Installation, Mounting / removal – Westermo GDW-11 User Manual
Page 23

23
6615-2203
This unit uses convection cooling. To avoid obstructing
the airflow around the unit, use the following spac-
ing rules. Minimum spacing 25 mm (1.0 inch) above
/ below and 10 mm (0.4 inches) left /right the unit.
Spacing is recommended for the use of unit in full
operating temperature range and service life.
Mounting
This unit should be mounted on 35 mm DIN-rail, which is
horizontally mounted inside an apparatus cabinet, or similar.
Snap on mounting, see figure.
Removal
Press down the black support at the top of the unit. See figure.
Installation
Mounting / Removal
Before mounting or removing the unit:
Warning! Do not open connected unit
Hazardous voltages may occur within this unit when connected to a power
supply.
Warning!
Prevent access to hazardous voltages by disconnecting the unit from its
power supply.
Warning!
Prevent damage to internal electronics from electrostatic discharges (ESD)
by discharging your body to a grounding point (e.g. use of wrist strap).
!
CLICK!
CLICK!
10 mm *
(0.4 inches)
25 mm
25 mm
* Spacing (left/right) recommended for
full operating temperature range