WattMaster WCC III part 14 User Manual
Page 30
WCC III Technical Guide
13B-28
13B. WCC III - MCD INSTALLATION GUIDE
MCD-Menu Program
Test APC UPS Connection (Choice #5)
This function will call the apcaccess program and display the
results in two columns. If no APC brand Smart UPS is present, a
message stating check UPS connection will appear.
*************************************************
*
Check USB Cable to UPS Connection.
*
*
*
******************************************
This message indicates that the UPS is not present and/or the
APCUPSD server did not start at system bootup. That would
be likely if the UPS cable was added after the installation of the
WCCIII-MCD2. Option 6 of the mcd-menu program will restart
the APC Monitor server after the connection is determined to
be true. Upon successful query of the APC UPC, the following
messages will appear:
Displaying the MCD’s UPS Monitoring Status.
Followed by:
*************************************************
*
UPS is online.
*
*
*
******************************************
APC
: 001,038,1006
HITRANS
: 141.0 Volts
DATE
: 2013-09-26 09:47:01 -050
ALARMDEL
: 30 seconds
HOSTNAME
: it-cv-lx
BATTV
: 13.7 Volts
VERSION
: 3.14.10 (13 September 20
LASTXFER
: Automatic or explicit se
UPSNAME
: APC
NUMXFERS
: 1
CABLE
: USB Cable
XONBATT
: 2013-09-25 12:52:13 -050
DRIVER
: USB UPS Driver
TONBATT
: 0 seconds
UPSMODE
: Stand Alone
CUMONBATT
: 8 seconds
STARTTIME
: 2013-09-11 13:37:00 -050
XOFFBATT
: 2013-09-25 12:52:21 -050
MODEL
: Back-UPS RS 700G
LASTSTEST
: 2013-09-25 12:52:13 -050
STATUS
: ONLINE
SELFTEST
: NO
LINEV
: 117.0 Volts
STATFLAG
: 0x07000008 Status Flag
LOADPCT
: 35.0 Percent Load Capac
SERIALNO
: 3B1120X45754
BCHARGE
: 100.0 Percent
BATTDATE
: 2011-05-13
TIMELEFT
: 15.9 Minutes
NOMINV
: 120 Volts
MBATTCHG
: 5 Percent
NOMBATTV
: 12.0 Volts
MINTIMEL
: 3 Minutes
NOMPOWER : 420 Watts
MAXTIME
: 0 Seconds
FIRMWARE
: 856.L3 .D USB FW:L3
SENSE
: Medium
END APC
: 2013-09-26 09:47:02 -050
LOTRANS
: 088.0 Volts