13B. WCC III - MCD2 INSTALLATION GUIDE

WCC III Technical Guide

13B-15

The 4 Line by 20 Character LCD screen

on the WCCIII-MCD2

The CrystalFontz – 4 by 20 line LCD is an end user viewing
interface that is used to show the current status of the WCCIII-
MCD2.

This 4 by 20 line LCD display will currently show the following
options:

IP address (Current IP confi guration for eth0 of the
WCCIII-MCD2)

System Time (Current time and date of the
WCCIII-MCD2)

System Uptime WCCIII-MCD2 Uptime (Time
since last reboot)

CPU Load Main processor CPU utilization (User
%, System%, Nice %, and Idle %)

NetLoad IP packet processing utilization (RX
(Incoming), and TX (Outgoing) packet processing)

POWER ON and POWER OFF status

The four status LEDs to the left of the LCD display the following:

Top LED – Labeled “POWER” – Displays the On/
Off/Running condition of the WCCIII-MCD2.
LED stays “RED” during initial power up or when
manually powered down, then turns “YELLOW”
and then “GREEN” during the self-test boot
up sequence. When the SBC and BackTask
are functioning, the LED will turn “GREEN”
to indicate that the WCCIII-MCD2 is fully
functioning.

2nd from Top LED – Labeled “BACKTASK” –
This LED displays the On/Off Condition (Running
or not Running) of the Backtask program. If
the LED is RED – the Backtask program is not
running. If the LED is Green – the Backtask
program is running normally.

3rd from top LED – Labeled “Network” and
is bi-color. Red LED means no connectivity.
“YELLOW” LED means access to the local Intra-
net has been made. GREEN LED means that
connection to the Internet has been made.

Bottom LED – Labeled “EMAIL” – Normal Status
for this LED is to Off, and this LED will turns
Green for fi ve seconds every time an EMAIL is
sent from the WCCIII-MCD2. On initial power up
this LED will turn “YELLOW” then “GREEN”
during the self-test boot up sequence

LCD Display

The CrystalFontz LCD module also used control the ATX (Power
Supply ON/OFF) type functionality of the PCM-9362N SBC
through the “H1” output connector which connects to the back
to inputs on the PCM-9362N SBC through the 50 pin “SBC
INTERNAL I/O CABLE” assembly.

The LCD’s Keypad

The LCD Keypad is used for the LCD screen navigation and to
control startup (power ON), Shutdown (power OFF), and reset of
the WCCIII-MCD2 device.

Starting the WCCIII-MCD2

Press and hold the Green Checkmark button for 1 second. The LCD
display will momentarily display, “Power On” before starting.

The WCCIII-MCD2 will automatically restart upon the application
or resumption of power after a power outage.

Resetting the WCCIII-MCD2

Press and hold the Green Checkmark button for 4 seconds. The
LCD display will momentarily display “Reset” before Reset
occurs.

Shutting Down the WCCIII-MCD2 - Soft Shut Down

Press and hold the Red X button for 4 seconds. The LCD display
will then display, “Power Off” during the Power Off period.

Forced Shut Down of the WCCIII-MCD2 - Hard Shut

Down

Press and hold the Red X button for 8 seconds. The LCD display
will then display, “Power Off” during the Power Off period. Files
are still open.