Chapter 4 - Signals and Troubleshooting
IV A
4 - 12
DCS 500B / DCP 500B Operating Instructions
4.5 Alarm Signals (A)
The alarm signals will be shown on the seven segment display of
the control board SDCS-CON-x as codes A . . as well as on the
LCD of the control panel CDP 31x as plain text. Alarm signals will
only be displayed, if there is no fault signal active.
The alarm signals - with the exception of
A 101
and
A 102
- will not
result in switching off the signal 10910 resp. in stopping the drive.
Code
seven
segm.
display
Text on
LCD of control panel
CDP 31x
Definition /
Possible source
Signal
number
(ALARM_WORD_1/2)
Remark
A 101 Start inhibition
Alarm Start Inhibition
Pin
908
(START_INHIBIT) is set to logical
"1“; drive cannot be switched ON.
When pin is set to logical "0“, the alarm sig-
nal will be reset.
11104
bit 0
A 102 Emergency stop
Alarm EMERGENCY STOP
Pin
906
has a logical "0" level; for signal re-
set, see introductory remarks in Chapter 4.4
"Fault Signals“ and Chapter 3.7 "EMER-
GENCY STOP RESETTING“.
11104
bit 1
A 103 Motor 1 temp. alarm
Alarm Overtemperature
MOTOR 1
Check: - Parameter setting MOT1.TEMP_
ALARM_L
[P 1402]
correct?
See also Fault Code
F 6.
11104
bit 2
A 104 Motor 1 overl.alarm
Alarm Overload
MOTOR 1 (Thermal Model 1)
Check: - See Fault Code
F 7.
11104
bit 3
A 105 Conv. overtemp.
alarm
Alarm Overtemperature
Power Section
This signal will already appear at approx.
10 °C below the shutdown temperature ap-
plying for Fault Signal
F 4
(see
P 10512
).
Check: - See Fault Code
F 4
.
11104
bit 4
A 106 Current reg blocked
Alarm Current Regulator/Controller blocked
Pin 404 (BLOCK) is set to logical "1“.
When pin is set to logical "0“, the alarm sig-
nal will be reset.
11104
bit 5
3ADW000055R0401_DCS500B_Operating Instruction_e_d