Chapter 4 - Signals and Troubleshooting
IV A
4 - 6
DCS 500B / DCP 500B Operating Instructions
Code
seven
segm.
display
Text on
LCD of control panel
CDP 31x
Definition /
Action
Status
signal
(FAULT_WORD_1/2)
Remark
F 20
Local & discon-
nected
No communication between CDP 31x/CMT
and DCS 500B / DCF 500B or DCP 500B in lo-
cal control mode
(LOCAL)
Check: - Connection cable between
CDP 31x – DCS 500 / DCP 500
(unplug connection cable from
CDP 31x and plug in again);
- Communication board SNAT 6xx
and appropriate programm O.K.?
- Local mode terminated when
panel/PC was removed?
11102
bit 11
(1)
Self re-
setting
F 21
Ext.Overvolt.Fault
Overvoltage protection DCF 506 has acted
There was an overvoltage condition in the
DC circuit of the field supply, which had been
limited by the activation of a free wheeling
circuit.
Check: - Power wiring of the field supply
- Control logic according to wiring
example?
- Does PP_DI_OVP [1216] has been
connected to a binary input?
- Setting of OVP_SELECT [1217]
correct? (see Alarm 121)
11103
bit 12
(1)
S21.232
and
higher
F
23
Motor stalled
Motor stalled
While starting the motor the current exceeded
the value of parameter
[P 2207]
for a time
longer than parameter
[P 2208]
and the speed
feedback value was below parameter
[P 2206]
.
Check: - Motor stalled?
- Load changed during start?
- Correct field current?
-
Current/torque
limitation;
-
Parameter
settings
[P 22xx].
11102
bit 14
(3)
F 27
Motor 2 overload
Overload of MOTOR 2
(Thermal model
2
).
{see Fault Code
F 7
}
11101
bit 9
(2)