Chapter 4 - Signals and Troubleshooting

IV A

4 - 4

DCS 500B / DCP 500B Operating Instructions

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Action

Status

signal

(FAULT_WORD_1/2)

Remark

F 3

Conv.fan curr.fault

Current converter fan not within limits

The current of the converter´s cooling fan is
measured via the option board PW1002/3.
Check: - Fan supply, fan current;

- Setting of PW1002,

SET_MAX_BR_TEMP

[P519] and

CONV_TEMP_DELAY

[P527]

- Direction of rotation, fan compo

nents, air inlet

11103

bit 11

(1)

S21.232

and

higher

F 4

Converter overtemp.

Overtemperature power section

Check: - Fan supply, direction of rotation,

fan components, air inlet and

ambient

temperature;

- Inadmissible load cycle?

11101

bit 3

(2)

F 5

Earth fault

Earth fault

(

Σ

I differs from zero)

Disconnect the mains and verify zero voltage
in armature and field circuits.
Make insulation test for the complete
installation.

Check sum current transformer; if necessary,
change transformer and SDCS-IOB-3 board.

11101

bit 4

(1)

F 6

Motor 1 overtemp.

Overtemperature of MOTOR 1

Check: - Temperature sensor and its

cabling;

- Motor cooling or sizing;

- Inputs for temperature sensor

on board SDCS-IOB-3;

-

Parameter

setting

MOT1.TEMP_

FAULT_L [P 1403]

correct?

Note: It will only be possible to reset this fault signal when the
motor temperature has fallen below the threshold which is
valid for the

alarm signal A 103; the signal will also be

evaluated while the mains contactor is de-energized (open).

11101

bit 5

(2)

F 7

Motor 1 overload

Overload of MOTOR 1

(Thermal model

1

)

Check: - Motor temperature (let motor cool

down and restart);

- Motor ratings and parameters of

thermal

model;

- Motor sizing or load cycle.

11101

bit 6

(2)