Chapter 2 - Start-Up Instructions
DCS 500B / DCP 500B Operating Instructions
IV A
2 - 11
Drive must not turn!
Do not preset an external reference!
1201 = 3
Panel display: ARM. AUTOTUNING
Activate the current controller's auto-tuning function.
Start the next two steps within the next 20 seconds!
Switch ON power.
DANGER: System components now energized!
Start drive.
When the display shows NOT ACTIVATED (action correctly completed),
stop drive; it may happen that the unit runs armature-circuit current since
e.m.f. control is active; n
min
- signal (2201)
⇒
value too small.
Switch OFF power!
Read out values of:
407 = ............ 408 = ............ 409 = ............ 410 = ............ 411 = ............
Use values of 409 and 410 from the first auto-tuning routine.
Re-activate the field unit used by entering:
a)
505 = 1
Panel display: DIODE FIELD EXCIT
and install the supply fuses removed before!
or
b)
505 = 2
Panel display: FEX2 OR FEX3
CAUTION! Please don't forget!
11202 = SAVE MOT1 SET
Save the altered values in the non-volatile memory!
3ADW000055R0401_DCS500B_Operating Instruction_e_d