Chapter 4 - Signals and Troubleshooting

IV A

4 - 10

DCS 500B / DCP 500B Operating Instructions

Code

seven

segm.

display

Text on

LCD of control panel

CDP 31x

Definition /

Action

Status

signal

(FAULT_WORD_1/2)

Remark

F 44

I/O-Board not found

Missing input/output (I/O-) boards
IOB1/2x/3/IOE1

The existance of the boards had been recog-
nized by the software and something hap-
pened to the board or the cable.

Check: - Is +/- 10 V supply available?

- Flat cable connections between

SDCS-CON-x and SDCS-IOB-1/2x/3/IOE1

11101

bit 7

(1)

Can

not be

reset

F 48

Motor 2 overtemp.

Overtemperature of MOTOR 2

Check: - Parameter setting

MOT2 TEMP_

FAULT_L [P 1603]

correct?

{See Fault Code

F 6

}

11101

bit 8

(2)

F 50

No C FAN ack

No CONVERTER FAN supply acknowledge

Depending on type of unit (size):

Size C4

Fault

signal

F 50

Sizes C1/C2/A5

Alarm

signal

A 126

Check: - Was input for acknowledge

signal

(parameter

[P 910]

) used?

{See Fault Code

F 40

}.

11102

bit 10

(2)

F 52

No BRAKE ack

No BRAKE acknowledge

Check: - Was parameter

[P 304]

used?

- Cabling and limit switches.

11101

bit 10

(2)

F 60

Fieldbus Timeout

Serial interface (communication bus) is not
O.K.

Check: - Does a field bus module selected

via

parameter

[P 4001]

exist?

- Communication between control

system and module

Nxxx-0x

O.K.?

No or incomplete telegrams?

- Communication between module

Nxxx-0x

and thyristor power con-

verter

O.K.?

- Correct setting of the time inter-

val between two telegrams via

parameter

[P 921]

?

11103

bit 13

/(3)

De-

pends

on

[P 920]