Tecfluid XT5 User Manual
Page 6

6
To configure the analog output type (active or passive) there is a slide switch situated just
behind the terminal strip. For the passive mode the switch must be towards the positive
terminal and for active mode the switch must be towards the negative terminal. To move
the switch use the point of a small screwdriver.
In the case of using HART communication the output mode should be passive. Normally a
HART master is active.
NOTE:
The analog output has protection against reversed polarity. Due to another
protection against over voltages, if a loop supply voltage of greater than 32 V is connected
the equipment may be damaged.
Possibilities of connection for the power supply and analog output
Active
indicator
e. g. PLC
Passive output