Connection points for a hart, Terminal or a pc with hart, Modem power supply 18 to 36 v – Tecfluid XT5 User Manual
Page 17
![background image](https://www.manualsdir.com/files/807347/content/doc017.png)
Summary of the principal communication characteristics:
17
Manufacturer, Model and Revision
Tecfluid S.A., XT5 converter, Rev. 1
Device type
Transmitter
Hart Revision
6.0
Device Description available
No
Number and type of sensors
1, exterior
Number and type of actuators
0
Number and type of host side signals
1, 4 – 20 mA Analog
Number of Device Variables
2
Number of Dynamic Variables
1
Mappable Dynamic Variables
No
Number of Common Practice Commands
14
Number of Device Specific Commands
8
Bits of Additional Device Status
17
Burst mode?
No
Write Protection?
Yes
The detail of the characteristics with respect to the HART
TM
communication are available
in the corresponding “Field Device Specification” document.
To be able to use HART
TM
communication, a resistance (R ext.), whose value must not
be lower than 200 Ohms, should be added to the current loop. The points at which a
terminal or a PC with a HART
TM
modem can be connected are shown in the following
figure.
Connection points for a HART
TM
terminal
or a PC with HART
TM
modem
Power
Supply
18 to 36 V