Summary of the principal communication characteristics:

17

Manufacturer, Model and Revision

Tecfluid S.A., XT5 converter, Rev. 1

Device type

Transmitter

Hart Revision

6.0

Device Description available

No

Number and type of sensors

1, exterior

Number and type of actuators

0

Number and type of host side signals

1, 4 – 20 mA Analog

Number of Device Variables

2

Number of Dynamic Variables

1

Mappable Dynamic Variables

No

Number of Common Practice Commands

14

Number of Device Specific Commands

8

Bits of Additional Device Status

17

Burst mode?

No

Write Protection?

Yes

The detail of the characteristics with respect to the HART

TM

communication are available

in the corresponding “Field Device Specification” document.
To be able to use HART

TM

communication, a resistance (R ext.), whose value must not

be lower than 200 Ohms, should be added to the current loop. The points at which a
terminal or a PC with a HART

TM

modem can be connected are shown in the following

figure.

Connection points for a HART

TM

terminal

or a PC with HART

TM

modem

Power

Supply

18 to 36 V