12 PROGRAMMING

DIAGRAM

Problem

Probable cause

Remedy

The display is blank

Fused fuse.

Change the fuse.

The analog output gives
always 4 mA or 20 mA

Current output range not properly
programmed.

Program the range properly (see
page 9).

The analog output gives
0 mA

Cable disconnected

Check the cable connection

The pulse output does
not work well

In pulse / unit of volume mode, the
frequency is higher than 6,25 Hz

Decrease the pulses / unit of
volume or change to frequency
output mode (see page 9).

The totalizer does not
change its value

The flow rate is negative (with
respect to the fluid direction)

Program the positive flow rate
direction according to the fluid
direction (see page 11).

The keys do not act

The keys are locked “write protect”

Unlock the keys by placing the
jumper (see page 13).