M4557 - Model 9210 Nitriding Controller

SSi Manual SERIES 9210-M4557-Nitriding

Page 35 of 35

The next screen is the Zero Input 3 Range 2 screen.

This screen will allow the user to set the zero scale
for Input 3 Range 2. A value of 0 millivolts will need

to be sourced to the inputs. For a zero calibration,

enter a 0 as the value of the terminal to correctly

calibrate the inputs. The current Input 3 value will

be displayed near the bottom of the screen as

“Current Input 3 value: xxxx.xx uV”. The progress
bar at the bottom of the screen will display the

calibration progress.

The next screen is the Span Input 3 Range 2

screen. This screen will allow the user to set the

span value for Input 3 Range 2. A suggested
value will be displayed next to the Calibrate

button (“sugg. 65.000 mV”). The current Input 3

value will be displayed near the bottom of the

screen as “Current Input 3 value: xxxx.xx uV”.

The progress bar at the bottom of the screen will

display the calibration progress.

The next screen is the Zero Output 1 screen.

This screen will allow the user to set the zero

value for Output 1. Measured at terminals 24(-)
and 25(+) for this step. The progress bar at the

bottom of the screen will display the calibration

progress.


The next screen is the Span Output 1 screen. This

screen will allow the user to set the span value for
Output 1. Measured at terminals 24(-) and 25(+)

for this step. The progress bar at the bottom of the

screen will display the calibration progress.

The next screen is the Zero Output 2 screen. This

screen will allow the user to set the zero value for

Output 2. Measured at terminals 26(-) and 25(+)
for this step. The progress bar at the bottom of the

screen will display the calibration progress.

Edit

Zero Output 1

Calibrate

<-- Back

Skip

Next -->

DONE

Enter span output current (mA)

Edit

Span Output 1

Calibrate

<-- Back

Skip

Next -->

DONE

Entered measured output current (mA)

Edit

Zero Output 2

Calibrate

<-- Back

Skip

Next -->

DONE

Enter zero output current (mA)