Super Systems 7EK 31080 User Manual
Page 16
12
P15 = Alarm 3 operative mode
Available only when P14 is different from 0.
H.A. = High alarm (outside for band alarm) with
automatic reset.
L.A. =
Low alarm (inside for band alarm) with automatic
reset.
H.L. =
High alarm (outside band) with manual reset
(latched alarm).
L.L. =
low alarm (inside band) with manual reset
(latched alarm).
P16 =
Programmability of the alarm 3.
Available only when P14 is different from 0.
OPrt =
Alarm 3 threshold and hysteresis are
programmable in operating mode.
COnF =
Alarm 3 threshold and hysteresis are
programmable in configuration mode.
P17 =
Alarm 3 threshold value
Available only when P14 is different from 0 and P16 is
equal to "COnF".
Range:
- For process alarm
- within the span limits (P4 - P3)
- For band alarm
- from 0 to 500 units.
- For deviation alarm
- from -500 to 500 units.
P18 =
Alarm 3 hysteresis value
Available only when P14 is different from 0 and P16 is
equal to "COnF".
Range: from 0.1% to 10.0 % of the span (P4 - P3)
P19= Soft Start threshold
Threshold value, in eng. units, to initiate the "Soft start"
function (output power limiting) at start up.
Range: within the readout span.
NOTE: this threshold value will not be taken into account
when tOL = InF.
P20 = Safety lock
0 =
No parameter protection. The device is always in
unlock condition and all parameters can be modified.
1 =
The device is always in lock condition and no one of
the parameters (exception made for set points [SP,
SP2] and alarm manual reset) can be modified (for
SMART status see P31 parameter).
From 2 to 4999 =
This combination number is a secret
value to be used, in run time (see nnn parameter) to
put device in lock/unlock condition.
For SP, SP2 and manual reset of the alarms, the
lock/unlock condition has no effect (for SMART
status see P31).
From 5000 to 9999 = This combination number is a secret
value to be used, in run time (see nnn parameter) to
put device in lock/unlock condition.
For SP, SP2, manual reset of the alarm, AL1, AL2,
AL3, Hbd and SCA, the lock/unlock condition has no
effect (for SMART status see P31).
NOTE: when safety lock is selected, the secret value can
not be displayed anymore and the display will show 0, 1,
SFt.A (when P20 is encompassed between 2 and 4999)
or SFt.b (when P20 is encompassed between 5000 and
9999)
P21 = Alarm 1 action
Available only when P7 is different from 0 or 4.
dir
= direct action (relay energized in alarm condition)
rEV = reverse action (relay de-energized in alarm
condition)
P22 = Alarm 1 stand-by function (mask)
Available only when P7 is different from 0 or 4.
OFF = stand-by function (mask alarm) disabled
On = stand-by function (mask alarm) enabled
NOTE: If the alarm is programmed as band or deviation
alarm, this function masks the alarm condition after a set
point change or at the instrument start-up until process
variable reaches the alarm threshold plus or minus
hysteresis. If the alarm is programmed as a process
alarm, this function masks the alarm condition at
instrument start-up until the process variable reaches the
alarm threshold plus or minus hysteresis.