9
c) Push “FUNC” push-button. The instrument ends the
configuration modify mode, preforms an automatic
reset and restarts in the run time mode.
Pushbutton function during configuration mode
FUNC =
This will memorize the new value of the
selected parameter and go to the next
parameter (increasing order).
MAN =
This will scroll back the parameters without
memorization of the new value.
s
=
This will increase the value of the selected
parameter
t
=
This will decrease the value of the selected
parameter.
CONFIGURATION PARAMETERS
Notes:
1) In the following pages we will describe all the
parameters of the instrument but the instrument will
show only the parameters related with the specific
hardware and in accordance with the specific
instrument configuration (i.e. setting OUT 3 equal to 0
(not used), all the parameters related with alarm 2 will
be skipped).
2) During configuration mode, the lower display shows
the mnemonic code of the selected parameter while
the upper display shows the value or the status
assigned to the selected parameter.
dF.Cn = Default configuration parameter
loading
Available in modify configuration parameters only
OFF = No loading data
tb1
= Loading European Table default parameters.
tb2
= Loading American Table default parameters.
NOTE: the list of both default parameter tables is reported
at Appendix A.
SEr1 = Serial interface protocol
OFF
= No serial interface
Ero
= Polling/selecting ERO
nbUS
= Modbus
jbUS
= Jbus
SEr2 = Serial link device address
Not available when SEr1 = OFF
From 1 to 95 for ERO protocol
From 1 to 255 for all the other protocols
NOTE: the electrical characteristic of the RS 485 serial
interface will allow the connection of 31 devices
maximum.
SEr3 = Baud rate for serial link
Not available when SEr1 = OFF
From 600 to 19200 baud.
NOTE: 19200 baud is shown on display as 19.20.
SEr4 = Byte format for serial link
Not available when SEr1 = OFF
7E
= 7 bits + even parity (For ERO protocol only)
7O
= 7 bits + odd parity (For ERO protocol only)
8E
= 8 bits + even parity
8O
= 8 bits + odd parity
8
= 8 bits without parity
P1 - Input type and standard range
0
= TC type
L
range
0 /
+400.0 °C
1
= TC type
L
range
0 /
+900 °C
2
= TC type
J
range
-100.0 /
+400.0 °C
3
= TC type
J
range
-100 /
+1000 °C
4
= TC type
K
range
-100.0 /
+400.0 °C
5
= TC type
K
range
-100 /
+1370 °C
6
= TC type
N
range
-100 /
+1400 °C
7
= TC type
R
range
0 /
+1760 °C
8
= TC type
S
range
0 /
+1760 °C
9
= RTD type
Pt 100
range
-199.9 /
+400.0 °C
10 = RTD type
Pt 100
range
-200 /
+800 °C
11 = mV
Linear
range
0 /
60 mV
12 = mV
Linear
range
12 /
60 mV
31080-1-00.p65
3/24/00, 11:58 AM
9