Super Systems 7EK 31080 User Manual
Page 14
10
13 = mA
Linear
range
0 /
20 mA
14 = mA
Linear
range
4 /
20 mA
15 = V
Linear
range
0 /
5 V
16 = V
Linear
range
1 /
5 V
17 = V
Linear
range
0 /
10 V
18 = V
Linear
range
2 /
10 V
19 = TC type
L
range
0 /
+1650 °F
20 = TC type
J
range
-150 /
+1830 °F
21 = TC type
K
range
-150 /
+2500 °F
22 = TC type
N
range
-150 /
+2550 °F
23 = TC type
R
range
0 /
+3200 °F
24 = TC type
S
range
0 /
+3200 °F
25 = RTD type
Pt 100
range
-199.9 /
+400.0 °F
26 = RTD type
Pt 100
range
-330 /
+1470 °F
27 = TC type
T
range
-199.9 /
400.0 °C
28 = TC type
T
range
-330 /
750 °F
NOTE: selecting P1 = 0, 2, 4, 9, 25 or 27, the instrument
set automatically P40 = FLtr. For all the remaining ranges
it will set P40 = nOFL.
P2 = Decimal point position
This parameter is available only when a linear input is
selected (P1 = 11 to 18).
----.
= No decimal figure.
---.-
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
1) When this parameter is modified, rL parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be greater than P4 in order to get a reverse
readout.
P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.
Notes:
1) When this parameter is modified, rH parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be smaller than P3 in order to get a reverse
readout.
The initial and full scale values determine the input span
which is used by the PID algorithm, the SMART and the
alarm functions.
NOTE: the minimum input span (S = P4 - P3), in absolute
value, should be set as follows:
- For linear inputs, S > 100 units.
- For TC input with °C readout, S > 300 °C.
- For TC input with °F readout, S > 550 °F.
- For RTD input with °C readout, S > 100 °C.
- For RTD input with °F readout, S > 200 °F.
P5 = Output 1 type
Changing the P5 setting, also Cy1 parameter will be
automatically modified.
rEL = Relay [the cycle time (Cy1) will be forced to
15 s]
SSr = SSR [the cycle time (Cy1) will be forced to 4 s]
P6 = Output 1 action
This parameter is skipped if P7 = 4
rEV = Reverse action (Heating action)
dir = Direct action (Cooling action)
t
INPUT
t
OUTPUT
t
INPUT
t
OUTPUT
Reverse
Direct
31080-1-00.p65
3/24/00, 11:58 AM
10