In multiple heater applications

multiple heater applications

multiple heater applications

multiple heater applications, the combustion air intake may be ducted individually or common ducted in the

same configuration as shown for venting in Section 17.0). For combustion air intake duct sizing, please refer to
the Vent Sizing Table

Vent Sizing Table

Vent Sizing Table

Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.

Flue vent termination

must be 1 ft. (30 cm)

higher than combustion

air inlet cap.

Flue

Vent

SIDE VIEW

ETS SHOWN

Combustion

Air Intake

Combustion Air Cap

(Leslie VersaCap

Type B)

6” Diameter

Single-Wall Pipe

Flashing

1/4” (6mm) fall per ft. (0.3m)

toward vent terminal

Horizontal

Through Sidewall

6” (15cm)

Minimum

6” Starting Collar

(field supplied)

3 ft. (91cm)

Minimum

Vertical

Through the roof

Control Box

Perforated Cover

(Remove)