beautypg.com

Primetest 200, Operating instructions 19 – Seaward 200 PrimeTest User Manual

Page 29

background image

IEC Insulation

Intrinsic Error or

Reference Conditions or

Code

Max Error

Influence Quantity

Rated Operating Conditions

Seen

Intrinsic Error

Reference Condions

A

5%

Position

Reference Positions ±90°

E

1

N/A

Supply Voltage

At the Limits Specified

E

2

1%

by the Manufacturer

Temperature

0°C and 35°C

E

3

1%

Absorbed Current of

Maximum Absorbed Current

Device on Test

of the Device on Test

E

4

N/A

Low-frequency

Low-frequency

Magnetic Field

Magnetic field 0.4 kA/m

E

5

N/A

Not Used

Not Used

E

6

N/A

Capacitance

Cmax = 1uF

E

7

N/A

Waveform

R.M.S. CR <= 2

E

8

N/A

Operating Error

B=\A\+1.15

E

1

2

+E

2

2

+E

3

2

+E

4

2

+E

5

2

+E

6

2

+E

7

2

+E

8

2

6.63%

PrimeTest 200

Operating Instructions

19

Class 2 Insulation

Intrinsic Error or

Reference Conditions or

Code

Max Error

Influence Quantity

Rated Operating Conditions

Seen

Intrinsic Error

Reference Condions

A

5%

Position

Reference Positions ±90°

E

1

N/A

Supply Voltage

At the Limits Specified

E

2

0.53%

by the Manufacturer

Temperature

0°C and 35°C

E

3

1%

Absorbed Current of

Maximum Absorbed Current

Device on Test

of the Device on Test

E

4

N/A

Low-frequency

Low-frequency

Magnetic Field

Magnetic field 0.4 kA/m

E

5

N/A

Not Used

Not Used

E

6

N/A

Capacitance

Cmax = 1uF

E

7

N/A

Waveform

R.M.S. CR <= 2

E

8

N/A

Operating Error

B=\A\+1.15

E

1

2

+E

2

2

+E

3

2

+E

4

2

+E

5

2

+E

6

2

+E

7

2

+E

8

2

6.30%

Point to Point Resistance

Intrinsic Error or

Reference Conditions or

Code

Max Error

Influence Quantity

Rated Operating Conditions

Seen

Intrinsic Error

Reference Condions

A

5%

Position

Reference Positions ±90°

E

1

N/A

Supply Voltage

At the Limits Specified

E

2

0.6%

by the Manufacturer

Temperature

0°C and 35°C

E

3

1.4%

Absorbed Current of

Maximum Absorbed Current

Device on Test

of the Device on Test

E

4

N/A

Low-frequency

Low-frequency

Magnetic Field

Magnetic field 0.4 kA/m

E

5

N/A

Not Used

Not Used

E

6

N/A

Capacitance

Cmax = 1uF

E

7

N/A

Waveform

R.M.S. CR <= 2

E

8

N/A

Operating Error

B=\A\+1.15

E

1

2

+E

2

2

+E

3

2

+E

4

2

+E

5

2

+E

6

2

+E

7

2

+E

8

2

6.75%