SERVICE DIAGNOSIS: Refrigeration and/or Mechanical

SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

Poor harvest

Hot gas valve does not open

Check for power to the coil, check
for not opening, replace

Head pressure control valve does
not maintain enough head
pressure.

Replace head pressure control
valve.

Unit cycles off during freeze or
harvest

Hi temperature switch opens and
closes

Hot gas valve leaks thru, replace it

Low capacity

High head pressure, from dirty
condenser, faulty fan motor

Clean condenser, repair fan
motor

Non condensable gas in the
system

Purge system, evacuate and
weigh in nameplate charge

Extreme hot location

Relocate the cabinet

Overcharge of refrigerant

Evacuate and weigh in nameplate
charge

Hot gas valve leaks thru

At the end of the freeze cycle
there should be frost on the
evaporator end of the hot gas
tubes, if not replace the hot gas
valve

Liquid and discharge lines are in
contact with each other

Separate and insulate them

Unit shuts off before bin is full

Bin thermostat adjusted to open
too soon.

Rotate knob on the thermostat
clockwise to a colder setting.

Compressor cycles on and off

Low pressure control opening and
closing

Check low side pressure, liquid
line valve must open and low side
pressure raise over 35 PSIG
before pump down control will
close to run compressor

Compressor overheats

TXV not letting enough refrigerant
into evaporators, adjust or
replace TXV

Mechanical fault with compressor,
replace compressor

Frost on compressor

Some frost will not hurt

Do nothing

TXV meters too much refrigerant

Adjust or replace TXV

CME650R

October 1994

Page 25