Page 20

background image

The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when loosening the
union nuts.

CAUTION

Connection of
refrigerant pipes

The on-site connection of the
refrigerant pipes is made at the
rear of the unit.

It may be necessary to fit a reducer
or flared adapter to the indoor
unit. These fittings are included
as standard with the indoor unit.
Once installed, the connections
should be made tight against va-
pour diffusion.

The following instructions describe
the installation of the refriger-
ant circuit and the assembly of
the indoor unit and the outdoor
component.

1. The required pipe diameters are

given in the table "Technical
data".

2. Remove the factory-fitted pro-

tective caps and union nuts on
the connections. These should
be used during installation.

3. Before flanging the refrigerant

pipes, ensure that the union nut
is fitted on the pipe.

4. Prepare the laid refrigerant

pipes as shown below
(Fig. 6+7).

Only employ tools and com-
ponents suitable for refrigera-
tion applications.

NOTE

Flanging tool

7 Flanging the refrigerant pipe

Refrigerant pipe

Deburrer

6 Deburring the refrigerant pipe

8 Correct flange shape

Tighten 1. spanner

Counter

2. spanner

9 Tighten the fitting

Tightening

torque:

“ 15-20 Nm
“ 33-40 Nm
“ 50-60 Nm
“ 65-75 Nm
“ 95-105 Nm

5. Verify that the shape of the

flange is correct(Figure 8).

6. First connect and hand-tighten

the refrigerant connections
to ensure they are correctly
seated.

7. Now fully tighten the fittings

using 2 suitably sized open-
ended spanners. Use one span-
ner to counter the force when
tightening the fitting (Figure
9)

.

8. Use insulation hoses which are

designed for this temperature
range and diffusion tight.

9. Lay the refrigerant pipes from

the indoor unit to the outdoor
component. In doing so, ensure

that they are sufficiently at-

tached and take measures for
the oil return, if necessary!

10. Observe the permitted bend-

ing radius for the refrigerant
pipes during installation. Never
bend a pipe twice in the same
place. Brittle pipes and potential
cracking are the consequences.

11. Use the wall or floor brackets

to fit the outdoor component
against structural parts ap-
proved to support the static
load (refer to the installation
instructions for the brackets).

REMKO RVD...DC

20