Data specific to outdoor unit

ML 263 DC AT

ML 353 DC AT

ML 523 DC AT

Power supply

V/Ph/

Hz

230 / 1~ / 50

Operating range, cooling

°C

+5 to +50

Operating range, heating

°C

+5 to +30

7)

Air flow rate, max.

m³/h

1800

1800

2200

Enclosure class

IP

24

Sound power level max.

dB (A)

64

64

62

Sound pressure level

5)

dB (A)

56

56

54

Refrigerant

6)

R 410A

Refrigerant, basic capacity

kg

0.80

0.80

1.25

Max. operating pressure

kPa

4200 / 1500

Refrigerant, additional quantity >5m

g/m

20

Refrigerant piping, max. length

m

25

25

30

Refrigerant piping, max. height

m

10

10

15

Refrigerant connection

Liquid line

Inche

s

(mm)

1/4 (6.35)

1/4 (6.35)

1/4 (6.35)

Refrigerant connection

Suction pipe

Inche

s

(mm)

3/8 (9.52)

3/8 (9.52)

1/2 (12.70)

Dimensions: H/W/D

mm

540/780/250

540/780/250

590/760/285

Weight

kg

29.50

29.50

35.0

From serial number

1306...

1308...

1310...

EDP no.

1633265

1633355

1633525

1)

Air inlet temp. TK 27°C / FK 19°C, outside temperature TK 35°C, FK 24°C, max. air flow volume,

5m pipe length

2)

Air inlet temp. TK 20°C, outside temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length

3)

The specified value is based on results from standard testing.

The actual consumption depends on the use and location of the unit

4)

The specified value is based on the average heating period

5)

At distance of 1m in the open air; specified values are maximum values

6)

Contains greenhouse gas in accordance with the Kyoto protocol, GWP 1975 (for further information, see chapter "Adding refrigerant")

7)

This can be extended to -15°C with the appropriate accessory kit