5.6

Oil return measures

If the outdoor unit is installed at a higher level than

the indoor unit, suitable oil return measures must

be taken. Usually, an oil pump bend is installed for

every 2.5 metres of height difference.

2

1

A

B

3

Fig. 30: Oil return measures

A: Outdoor unit

B: Indoor unit

1: One oil pump bend in suction pipe to outdoor

unit every 2.5 metres of height difference

2: Radius: 50mm

3: Max. 10m

5.7

Connection variants for the

indoor unit

The following connection variants can be used for

the refrigerant, condensate and control lines.

A

D

C

B

Fig. 31: Connection variants

A: Outlet on the wall, right

B: Outlet through the wall, right

C: Outlet through the wall, left

D: Outlet on the wall, left

5.8

Wall bracket for the indoor unit

A

B

C

D

E

F

G

H

I

J

Fig. 32: Mounting points for the wall bracket ML 263 DC IT-523 DC IT (front view, all dimensions in mm)

Unit type / dimensions

A

B

C

D

E

F

G

H

I

J

ML 263 DC IT-353 DC IT

400

400

245

195

50

50

60

339

306

95

ML 523 DC IT

470

470

320

265

70

70

55

415

365

105

All dimensions in mm. In each case the diameter of the pipe break-through is

Ø 65 mm

The wall bracket for the units must be attached with suitable screws and anchors.

REMKO ML...DC

26