beautypg.com

Remko ml...dc – REMKO ML 263 DC User Manual

Page 12

background image

Heating capacity ML 353 DC

0,00

1,00

2,00

3,00

4,00

5,00

12

7

2

0

-7

-10

-15

2

1

3

A

[°C]

Fig. 5: Performance curves, heating ML 353 DC (data for 20 °C indoor temperature)

A:

Outside temperature

1:

COP

2:

Heating capacity in kW

3:

Power consumption in kW

Outside temp. in °C

12

7

2

0

-7

-10

-15

Heating capacity in kW

3.75

3.30

3.14

2.98

2.65

2.49

2.15

Power consumption in kW

0.95

0.93

1.56

1.47

1.38

1.38

1.30

COP

3.96

3.54

2.01

2.03

1.93

1.81

1.65

Cooling capacity ML 353 DC

0,00

0,50

1,00

1,50

2,00

2,50

3,00

3,50

4,00

21

25

30

35

40

45

50

2

1

3

A

[°C]

Fig. 6: Performance curves, cooling ML 353 DC (data for 27/19 °C indoor temperature)

A:

Outside temperature

1:

EER

2:

Cooling capacity in kW

3:

Power consumption in kW

Outside temp. in °C

21

25

30

35

40

45

50

Cooling capacity in kW

3.12

3.32

3.35

3.23

2.77

2.63

2.56

Power consumption in kW

0.85

0.92

1.00

1.10

1.11

1.13

1.18

EER

3.65

3.60

3.34

2.94

2.49

2.32

2.17

REMKO ML...DC

12

This manual is related to the following products: