Fig. 35: Flanging the refrigerant piping

1: Flanging tool

Fig. 36: Correct flange shape

2

1

Fig. 37: Tightening the fitting

1: Tighten with the first open-ended spanner

2: Counter with the second open-ended spanner

Pipe dimension in

inches

Tightening torque in Nm

1/4"

15-20

3/8"

33-40

1/2"

50-60

5/8"

65-75

3/4"

95-105

6.3

Additional notes on connecting

the refrigerant piping

n

When combining the outdoor unit with some

indoor units, the procedure for connecting the

refrigerant piping may differ. Install the pro-

vided reducer or expansion fittings to the

indoor unit.

n

If the basic length of the connecting line

exceeds 5m, add refrigerant when commis-

sioning the system for the first time (see

chapter "Adding refrigerant").