Fault P1: Overvoltage/undervoltage protection AT tripped

Check whether the power supply is present and

correct. Is this normal?

NO

Switch the supply and try again as soon as this

is normal again.

YES

Check all electrical connections. Are they OK?

NO

Correct the electrical connections.

YES

Check the voltage between the P and N termi-

nals of the outdoor unit. This should be approx.

320V DC. Is this voltage present?

YES

Replace the outdoor unit motherboard.

Fault P2: Excessive temperature at the compressor

Check the indoor unit and outdoor unit heat

exchangers for cleanliness. Is the air exchange

guaranteed?

NO

Clean the respective heat exchanger.

YES

Switch the unit off for 10 minutes. Check

whether the unit starts up again normally.

NO

Check all electrical connections and the heat

gas probe T5.

YES

Check the fill level of the refrigerant. Is this cor-

rect?

NO

Check the unit for leaks and fill with new refrig-

erant.

YES

Refrigerant cannot circulate. Possibly due to

internal contamination or kinked lines.

Fault P3: Overcurrent protection on the compressor

Check all electrical connections. Are these cor-

rectly implemented?

NO

Replace the connections.

YES

Check the compressor windings. Are they OK?

NO

Replace the compressor.