Single Shot Mode

Pressing the unit’s Run/Stop button generates a single pulse with every press. Set the
following parameters in the 9250 application:

Within the System section:

o Select Single Shot mode.

Within the Channel section:

o Set channel mode to Normal.

o Enter the required pulse width and delay. Repeat for each output channel.
o

Enable the corresponding channels by clicking “Enabled” in the 9250 application.

Pressing the unit’s Run/Stop button will now generate one pulse out of every enabled channel.

System Burst Mode Function

The Run/Stop button

generates a stream of ‘N’ T

0

pulses, where the ‘N’ is specified by the

Burst parameter. The rate is specified by the Period parameter. Pressing the

Run/Stop

button

while the burst is in process will stop the output. After the burst has been completed, Pressing
the

Run/Stop

button will generate another burst of pulses. To generate a burst of pulses set

the following parameters in the 9250 application:

Within the System section:

o Select mode to be Burst.
o Set the Burst Count parameter field to produce the number of pulses desired
o Set the desired Period.

Within the Channel section:

o Set channel mode to Normal.

o Enter the required pulse width and delay. Repeat for each output channel.
o

Enable the corresponding channels by clicking “Enabled” in the 9250 application.

Pressing the unit’s Run/Stop button will now generate the predefined burst of pulses out of
every enabled channel.

System Duty Cycle Function

The Run/Stop button starts a continuous stream of T

0

pulses, which repeats

for ‘N’ pulses On

and ‘M’ pulses Off, where ‘N’ and ‘M’ are specified by the On/Off parameters respectively. The
rate at which the pulses are generated is controlled by the Period parameter. To generate a
stream of pulses which will

repeat for ‘N’ pulses On and ‘M’ pulses, set the following

parameters in the 9250 application:

Within the System section:

o Set the mode to Duty Cycle.
o Set the On parameter to number of pulses to produce during th

e on cycle (‘N’).

o Set the Off parameter to

number of pulses to suppress during the off cycle (‘M’).

o Set the desired Period.