Orion System BACnet Link User Manual
Page 9
BACnet® Link Interface
Technical Guide
9
VAV/CAV Instance Number Base
VAV/CAV BACnet® Property Identifier
The BACnet
®
Link amends the following property identity to BACnet®’s
property identifier.
BACnetPropertyIdentifier :
WattBacScheduleState ::= ENUMERATED {
NormalOperation
(0),
ForceOccupied
(1),
ForceUnoccupied
(2)
}
VavCavControlMode ::= ENUMERATE {
Unoccupied
(0),
RemoteContactOccupied
(1),
NormalScheduleOccupied
(2),
PushButtonOrZoneOverride
(3),
HolidayModeActive
(4),
UnoccupiedZoneDemand
(5),
RemoteScheduleOverride
(6),
CurrentOutputForceMode
(7),
SATHighOrLowCutOff
(8),
CO2OverrideInProgress
(9),
PurgeModeActive
(10)
}
VavCavControlStatusBits ::= BIT STRING {
AhuControlEconomizer
(0),
NoOutdoorAirTempSensor
(1),
CarbonDioxiodeSensorPresent
(2),
HeatCoolStagingDisabled
(3),
DehumidificationMode
(4),
ModGasIIConnected
(5),
ReheatIIConnected
(6),
}
VavCavConfigurationBits ::= BIT STRING {
CoolingDemand
(0),
HeatingDemand
(1),
CoolingEnabled
(2),
HeatingEnabled
(3),
EconomizerEnabled
(4),
FanInStartUpDelay
(5),
WarmUpModeActive
(6),
ProofOfFlow
(7),
HumidistatContact
(8),
ProofOfFlowConfig
(9),
ConstantVolumeConfig
(10),
HeatWheelConfig
(11),
HumiditySensorConfig
(12),
WetBulbSensorConfig
(13),
ReliefPressureConfig
(14)
}
Instance Number Base For VAV/CAV Controller
Parameter
Instance
Number
Base
Represented
By
Object
Limits
Alarm Status
17
Analog Input
CO2 Setpoint
42
Analog Value
0
8000
Configuration
13
Analog Input
Control Mode
11
Analog Input
Control Status
12
Analog Input
Control Temperature
19
Analog Input
Cooling Setpoint
1
Analog Input
Duct Static Pressure
9
Analog Input
Duct Static Setpoint
38
Analog Value
0.01
3
Economizer Position
14
Analog Input
External Relay Group #1
35
Analog Input
External Relay Group #2
36
Analog Input
External Relay Group #3
37
Analog Input
Heating Setpoint
2
Analog Input
Minimum Outside Air
Setpoint
39
Analog Value
1
99
Occupied Cooling Setpoint
32
Analog Value
0
90
Occupied Heating Setpoint
20
Analog Value
0
90
On Board Relay Group
34
Analog Input
Outdoor Air Humidity
10
Analog Input
Outdoor Air Sensor Offset
31
Analog Value
-10
10
Outdoor Air Temperature
8
Analog Input
Outdoor Air Wetbulb
3
Analog Input
Relief Pressure
18
Analog Input
Relief Pressure Setpoint
40
Analog Value
-0.3
0.3
Return Air CO2 Level
41
Analog Input
Return Air Sensor Offset
30
Analog Value
-10
10
Return Air Temperature
7
Analog Input
Schedule Force
33
Analog Value
0
2
Space Sensor Offset
28
Analog Value
-10
10
Space Temperature
5
Analog Input
Staging Deadband
23
Analog Value
0
10
Supply Air Cooling Setpoint
25
Analog Value
50
70
Supply Air Heating Setpoint
26
Analog Value
0
300
Supply Air Sensor Offset
29
Analog Value
-10
10
Supply Air Temperature
6
Analog Input
Temperature Demand
4
Analog Input
Unoccupied Cooling Setpoint
21
Analog Value
0
30
Unoccupied Heating Setpoint
22
Analog Value
-30
0
VFD Blower Fan
15
Analog Input
VFD Exhaust Fan
16
Analog Input
Warm Up Setpoint
27
Analog Value
50
90
Wetbulb Setpoint
24
Analog Value
0
80
Table 4: Instance Number Base Data For VAV/CAV