General information, Bacnet, Link interface 3 technical guide – Orion System BACnet Link User Manual
Page 3: Data sharing, Scheduling, Hardware specifications, Table 1: bacnet, Link interface technical data, Figure 1: bacnet, Link board components and dimensions
![background image](https://www.manualsdir.com/files/800442/content/doc003.png)
BACnet
®
Link Interface
3
Technical Guide
4.00”
4.50"
0.25”
0.25”
7.00"
7.50"
JP1
R1
ADDR.
2
1
C4
U1
EEPROM
NET-
WORK
LOOP
R4
U6
T
SHLD
R
C10
X2
C9
DRIVER
C12
U7
JP4
TERM.
R15
R1
1
R10
R18
RN2
LED
1
LED
2
LED
3
LED
4
NET
COMM
LOOP
COMM
U9
RN1
C7
U2
C2
C3
R3
YS101928
0.20 Dia.
Mounting Hole
Typ. 4 PL.
Mounting
Backplate
Network (MSTP)
Communications
Wiring Terminal
Local Loop
Communications
Wiring Terminal
Local Loop
Communications
Driver Chip
24 VAC Power
Terminals
Network
Communications
LED
Local Loop
Communications
LED
Power
LED
Network
Driver Chip
EPROM Chip
Pin 1 Indicator
Address Switch
RAM Chip
Pin 1 Indicator
TRANSLATOR BOARD
REV 0
U3
EPROM
C8
Q1
PWR
R20
D2
R17
R16
R13
C14
R14
JP3
WDOG
U10
C11
JP2
RAM
U5
U4
SERIAL #
C1
R5
L1
R6 R7
R12
D1
C16
C17
R19
U11
R21
D3
R23
C19
R22
+24VAC
GND
TB3
C13
R8
R9
U8
DRIVER
T
(-)
SHLD
R
(+)
C6
LOOP
LOCAL
C5
X1
VCC
VBAT
R2
The OE367-22 BACnet
®
Link provides bi-directional translation of
data and information between BACnet
®
devices and Orion VAV/CAV,
CW/HW and MUA II unit controllers.
Up to 16 total, Orion VAV/CAV, CH/HW, MUA II or any combination
of these controllers may be connected to each BACnet
®
Link. Up to 4
BACnet
®
Links can be used on a Orion Controls system allowing for
a maximum of 64 total controllers to be used.
Data Sharing
The BACnet
®
Link interface provides the following data sharing capa-
bilities:
•
Provides values from points on the Orion side of the
gateway to BACnet
®
devices as if the values were
originating from BACnet
®
objects.
•
Allows BACnet
®
devices to modify point values on the
Orion controller side of the BACnet
®
Link by using
standard BACnet
®
write services
Scheduling
•
Ability to allow BACnet
®
devices to send Schedule events
to the Orion controller side of the gateway by using
standard BACnet
®
services
Hardware Specifications
Table 1 below contains the hardware specifications for the BACnet
®
Link interface.
T echnical D ata
B A C net L oop
RS-485, Auto D etect H ost
M atching - 9600, 19200, 38400,
76800 B aud R ates
C ontroller L oop
RS-485, 960 0 B aud
P rotocol (B A Cnet Lo op)
M S/T P L an
P rotocol
(W attM aster L oop)
HSI O pen P rotocol
Token Passing
P ow er Input Voltage
24 V A C
P ow er C ons um ption
10 V A M axim um
O perating T em p
10
°
F to 149
°
F
O perating H um idity
90% R H N on-C ondensing
W eight
8 oz
Table 1: BACnet
®
Link Interface Technical Data
General Information
Figure 1: BACnet
®
Link Board Components and Dimensions