Programming - standard objects, Technical guide bacnet, Link interface 10 – Orion System BACnet Link User Manual
Page 10: Cw/hw instance number base
Technical Guide
BACnet
®
Link Interface
10
Programming - Standard Objects
VavCavOnBoardRelayBits ::= BIT STRING {
OnBoardRelay1
(0),
OnBoardRelay2
(1),
OnBoardRelay3
(2),
OnBoardRelay4
(3),
OnBoardRelqy5
(4),
}
VavCavExRelayGroup1Bits ::= BIT STRING {
ExpansionBoard1Relay1
(0),
ExpansionBoard1Relay2
(1),
ExpansionBoard1Relay3
(2),
ExpansionBoard1Relay4
(3),
ExpansionBoard2Relay1
(4),
ExpansionBoard2Relay2
(5),
ExpansionBoard2Relay3
(6),
ExpansionBoard2Relay4
(7),
}
VavCavExRelayGroup2Bits ::= BIT STRING {
ExpansionBoard3Relay1
(0),
ExpansionBoard3Relay2
(1),
ExpansionBoard3Relay3
(2),
ExpansionBoard3Relay4
(3),
}
VavCavExRelayGroup3Bits ::= BIT STRING {
ExpansionBoard4Relay1
(0),
ExpansionBoard4Relay2
(1),
ExpansionBoard4Relay3
(2),
ExpansionBoard4Relay4
(3),
}
VavCavAlarmBits ::= BIT STRING {
BadSpaceTempSensor
(0),
FanProvingAlarm
(1),
MechanicalCoolingAlarm
(2),
MechanicalHeatingAlarm
(3),
DirtyFilterDetected
(4),
HighSpaceTempAlarm
(5),
LowSpaceTempAlarm
(6),
}
CW/HW Instance Number Base
Instance Number Base For CW/HW Controller
Parameter
Instance
Number
Base
Represented
By
Object
Limits
Alarm Status
17
Analog Input
CO2 Setpoint
42
Analog Value
0
8000
Cold Water Position
44
Analog Input
Configuration
13
Analog Input
Control Mode
11
Analog Input
Control Status
12
Analog Input
Control Temperature
19
Analog Input
Cooling Setpoint
1
Analog Input
Duct Static Pressure
9
Analog Input
Duct Static Setpoint
38
Analog Value
Economizer Position
14
Analog Input
External Relay Group #1
35
Analog Input
External Relay Group #2
36
Analog Input
HCW Configuration
45
Analog Value
0
31
Heating Setpoint
2
Analog Input
Hot Water Position
43
Analog Input
Minimum Outside Air
Setpoint
39
Analog Value
0.01
3
Occupied Cooling Setpoint
32
Analog Value
0
90
Occupied Heating Setpoint
20
Analog Value
0
90
On Board Relay Group
34
Analog Input
Outdoor Air Humidity
10
Analog Input
Outdoor Air Sensor Offset
31
Analog Value
-10
10
Outdoor Air Temperature
8
Analog Input
Outdoor Air Wetbulb
3
Analog Input
Relief Pressure
18
Analog Input
Relief Pressure Setpoint
40
Analog Value
1
99
Return Air CO2 Level
41
Analog Input
-0.3
0.3
Return Air Sensor Offset
30
Analog Value
-10
10
Return Air Temperature
7
Analog Input
Schedule Force
33
Analog Value
0
2
Space Sensor Offset
28
Analog Value
-10
10
Space Temperature
5
Analog Input
Staging Deadband
23
Analog Value
0
10
Supply Air Cooling Setpoint
25
Analog Value
50
70
Supply Air Heating Setpoint
26
Analog Value
0
300
Supply Air Sensor Offset
29
Analog Value
-10
10
Supply Air Temperature
6
Analog Input
Temperature Demand
4
Analog Input
Unoccupied Cooling Setpoint
21
Analog Value
0
30
Unoccupied Heating Setpoint
22
Analog Value
-30
0
Vfd Blower Fan
15
Analog Input
Vfd Exhaust Fan
16
Analog Input
Warm Up Setpoint
27
Analog Value
50
90
Wetbulb Setpoint
24
Analog Value
0
80
Table 5: Instance Number Base Data For CW/HW