Bacnet® link interface technical guide 23 – Orion System BACnet Link User Manual
Page 23
BACnet® Link Interface
Technical Guide
23
BACnet
®
Services
Objects cannot be dynamically created or deleted by using BACnet
®
Services with the BACnet
®
Link .
BACnet
®
Segmented Requests
BACnet
®
Link does not support segmented requests.
BACnet
®
Segmented Responses
BACnet
®
Link does not support segmented responses.
List Of All Property Identifiers For Proprietary Objects
Property
Identifier
Property Name
Read Or Write
1024
Alarm_Status
R/O
1025
Control_Status
R/O
1026
Cooling_Deadband
R/W
1027
Cooling_Setpoint
R/O
1028
Control_Temperature
R/O
1029
Dew_Point_Reset_Limit
R/W
1030
Dew_Point_Setpoint
R/W
1031
Duct_Static_Setpoint
R/W
1032
Economizer_Position
R/O
1033
Enthalpy_Deadband
R/W
1034
External_Heat_Proportion_Band
R/W
1035
External_Heat_Position
R/O
1036
Heating_Deadband
R/W
1037
Heating_Setpoint
R/O
1038
Modulate_Gas_Valve_Position
R/O
1039
Occupied_Cooling_Setpoint
R/W
1040
Occupied_Heating_Setpoint
R/W
1041
Outdoor_Air_Cooling_Setpoint
R/O
1042
Outdoor_Air_Heating_Setpoint
R/O
1043
Not Used
-----
1044
Not Used
-----
1045
Outdoor_Air_Dew_Point
R/O
1046
Outdoor_Air_Dew_Point_Setpoint
R/O
1047
Outdoor_Air_Enthalpy
R/O
1048
Outdoor_Air_Enthalpy_Setpoint
R/O
1049
Outdoor_Air_Enthalpy_Deadband
R/O
1050
Outdoor_Air_Humidity
R/O
1051
Outdoor_Air_Sensor_Offset
R/W
1052
Outdoor_Air_Temperature
R/O
1053
Outdoor_Air_Wetbulb
R/O
1054
Reheat_Value_Position
R/O
1055
Relays
R/O
1056
Relief_Pressure
R/O
1057
Return_Air_Temperature
R/O
1058
Return_Air_Sensor_Offset
R/W
1059
Schedule_Force
R/W
Table 17: List Of All Property Identifiers
List Of All Property Identifiers For Proprietary Objects
Property
Identifier
Property Name
Read Or Write
1060
Space_Humidity
R/O
1061
Space_Humidity_At_Max_Supply
R/W
1062
Space_Humidity_At_Min_Supply
R/W
1063
Space_Sensor_Offset
R/W
1064
Space_Temperature
R/O
1065
Space_Temperature_At_Max_Supply
R/W
1066
Space_Temperature_At_Min_Supply
R/W
1067
Staging_Deadband
R/W
1068
Supply_Air_Cooling_Setpoint
R/W
1069
Supply_Air_Heating_Setpoint
R/W
1070
Supply_Air_Reset_Limit
R/W
1071
Supply_Air_Sensor_Offset
R/W
1072
Supply_Air_Setpoint
R/W
1073
Supply_Air_Temerature
R/O
1074
Temperature_Demand
R/O
1075
Unoccupied_Coolting_Setpoint
R/W
1076
Unoccupied_Heating_Setpoint
R/W
1077
Vfd_Blower_Fan
R/O
1078
Vfd_Exhaust_Fan
R/O
1079
Warm_Up_Setpoint
R/W
1080
Wetbulb_Setpoint
R/W
1081
Supply_Air_Setpoint_Mirror
R/O
1082
Enthalpy_Unit
R/O
1083
Fan_Speed_Unit
R/O
1084
Humidity_Unit
R/O
1085
Position_Unit
R/O
1086
Temperature_Unit
R/O
1087
Hot_Water_Position
R/O
1088
Cold_Water_Position
R/O
1089
Hcw_Configuration
R./W
1090
Duct_Static_Pressure
R/O
1091
Min_Outside_Air_Setpoint
R/W
1092
Relief_Pressure_Setpoint
R/W
1093
Return_Air_CO2_Level
R/O
1094
CO2_Setpoint
R/O
BACnet
®
Data Link Layer
BACnet
®
Link supports the following data link layer.
•
Master-Slave/Token Passing (MS/TP) LAN
Data Link Protocol
•
Tested with Allertons BACtalk
®
Router 200