Programming - Proprietary Objects
BACnet
®
Link Overview
The BACnet
®
Link provides the communications interface between the
Orion system and a BACnet
®
network. One BACnet
®
Link can support
up to sixteen controllers. The BACnet
®
Link connects to the BACnet
®
network using Master-Slave/Token Passing (MS/TP) LAN data link
protocol. Complete information regarding the BACnet
®
Link device
object can be found on pages 3 through 5 of this manual.
The BACnet
®
Link supports 3 different controller types (objects). These
are the Orion MUA II, VAV/CAV and the CW/HW controllers. The
sections that follow describe the properties for each controller (device
object).
MUA II Object
The information that follows describes the characteristics of the MUA
II Object. The properties for the MUA II Object are listed in Table 7.
Object Name
The Object Name for the MUA II controller is a 15 byte character string
that can be set through the BACnet
®
front end.
Object Type
The Object Type of the MUA II controller is MuaII or 258.
Object Instance Number
The Instance Number of the MUA II Object is determined by two vari-
able values. The first variable is the loop address setting on the BAC-
net
®
Link for the specific loop the MUA II controller resides on and the
second is the MUA II controller address. The BACnet
®
Link loop ad-
dress can be either 0, 1, 2 or 3. See Figure 3 at the front of this manual
for detailed information on the BACnet
®
Link loop address jumper set-
tings.
The second variable value used to calculate the Object Instance number
is the MUA II controller address and is determined by the address switch
settings on the MUA II controller. Valid address settings are 1 through
16.
See Table 10 at the end of this chapter for complete Object Instance
Number calculation information
Object Properties
The information and tables that follow detail the properties and prop-
erty identifiers for the MUA II Object.
Properties For The MUA II Controller
Property Name
Property Data Type
Property
Identifier
Read
Or
Write
Alarm_Status
MuaIIAlarmBits
1024
R/O
Application_Software_Version
Unsigned
11
R/O
Control_Status
MuaControlBits
1025
R/O
Cooling_Deadband
Unsigned
1026
R/W
Dew_Point_Reset_Limit
Unsigned
1029
R/W
Dew_Point_Setpoint
Unsigned
1030
R/W
Enthalpy_Deadband
Unsigned
1033
R/W
Enthalpy_Unit
BACnetEngineeringUnits
1082
R/O
External_Heat_Position
Real
1035
R/O
External_Heat_Proportion_Band
Unsigned
1034
R/W
Heating_Deadband
Unsigned
1036
R/W
Humidity_Unit
BACnetEngineeringUnits
1084
R/O
Modulate_Gas_Valve_Position
Unsigned
1038
R/O
Object_Identifier
BACnetObjectIdentifier
75
R/O
Object_Name
CharacterString
77
R/W
Object_Type
WattBacObjectTypes
79
R/O
Outdoor_Air_Cooling_Setpoint
Real
1041
R/O
Outdoor_Air_Dew_Point
Real
1045
R/O
Outdoor_Air_Dew_Point_Setpoint
Real
1046
R/O
Outdoor_Air_Enthalpy
Real
1047
R/O
Outdoor_Air_Enthalpy_Deadband
Real
1049
R/O
Outdoor_Air_Enthalpy_Setpoint
Real
1048
R/O
Outdoor_Air_Heating_Setpoint
Real
1042
R/O
Outdoor_Air_Humidity
Real
1050
R/O
Outdoor_Air_Temperature
Real
1052
R/O
Position_Unit
BACnetEngineeringUnits
1085
R/O
Reheat_Value_Position
Unsigned
1054
R/O
Relays
MuaIIRelayBits
1055
R/O
Schedule_Force
WattBacScheduleState
1059
R/W
Space_Humidity
Real
1060
R/O
Space_Humidity_At_Max_Supply
Unsigned
1061
R/W
Space_Humidity_At_Min_Supply
Unsigned
1062
R/W
Space_Temperature
Real
1064
R/O
Space_Temperature_At_Max_Supply
Unsigned
1065
R/W
Space_Temperature_At_Min_Supply
Unsigned
1066
R/W
Supply_Air_Reset_Limit
Unsigned
1070
R/W
Supply_Air_Setpoint
Unsigned
1072
R/W
Supply_Air_Setpoint_Mirror
Real
1081
R/O
Supply_Air_Temerature
Real
1073
R/O
Temperature_Unit
BACnetEngineeringUnits
1086
R/O
Table 7: MUA II Object Properties