BACnet® Link Interface

Technical Guide

15

Object Properties For The VAV/CAV Controller

Property Name

Property Data Type

Property
Identifier

Read

Or

Write

Alarm_Status

VavAlarmBits

1024

R/O

Application_Software_Version

Unsigned

11

R/O

CO2_Setpoint

Real

1094

R/O

Control_Status

VavControlBits

1025

R/O

Control_Temperature

Real

1028

R/O

Cooling_Setpoint

Real

1027

R/O

Duct_Static_Pressure

Real

1090

R/O

Duct_Static_Setpoint

Real

1031

R/W

Economizer_Position

Real

1032

R/O

Fan_Speed_Unit

BACnetEngineeringUnits

1083

R/O

Heating_Setpoint

Real

1037

R/O

Humidity_Unit

BACnetEngineeringUnits

1084

R/O

Min_Outside_Air_Setpoint

Real

1091

R/W

Object_Identifier

BACnetObjectIdentifier

75

R/O

Object_Name

CharacterString

77

R/W

Object_Type

WattBacObjectTypes

79

R/O

Occupied_Cooling_Setpoint

Unsigned

1039

R/W

Occupied_Heating_Setpoint

Unsigned

1040

R/W

Outdoor_Air_Humidity

Real

1050

R/O

Outdoor_Air_Sensor_Offset

Real

1051

R/W

Outdoor_Air_Temperature

Real

1052

R/O

Outdoor_Air_Wetbulb

Real

1053

R/O

Position_Unit

BACnetEngineeringUnits

1085

R/O

Relays

VavRelayBits

1055

R/O

Relief_Pressure

Real

1056

R/O

Relief_Pressure_Setpoint

Real

1092

R/W

Return_Air_CO2_Level

Real

1093

R/O

Return_Air_Sensor_Offset

Real

1058

R/W

Return_Air_Temperature

Real

1057

R/O

Schedule_Force

WattBacScheduleState

1059

R/W

Space_Sensor_Offset

Real

1063

R/W

Space_Temperature

Real

1064

R/O

Staging_Deadband

Integer

1067

R/W

Supply_Air_Cooling_Setpoint

Unsigned

1068

R/W

Supply_Air_Heating_Setpoint

Unsigned

1069

R/W

Supply_Air_Sensor_Offset

Real

1071

R/W

Supply_Air_Temperature

Real

1073

R/O

Temperature_Demand

Real

1074

R/O

Temperature_Unit

BACnetEngineeringUnits

1086

R/O

Unoccupied_Coolting_Setpoint

Unsigned

1075

R/W

Unoccupied_Heating_Setpoint

Unsigned

1076

R/W

Vfd_Blower_Fan

Real

1077

R/O

Vfd_Exhaust_Fan

Real

1078

R/O

Warm_Up_Setpoint

Unsigned

1079

R/W

Wetbulb_Setpoint

Unsigned

1080

R/W

Table 8: VAV/CAV Object Properties

VAV/CAV Object

The information that follows describes the characteristics of the VAV/
CAV Object. The properties for the VAV/CAV Object are listed in Table
8
.

Object Name

The Object Name for the VAV/CAV controller is a 15 byte character
string that can be set through the BACnet

®

front end.

Object Type

The Object Type of the VAV/CAV controller is VavCav or 257.

Object Instance Number

The Instance Number of the VAV/CAV Object is determined by two
variable values. The first variable is the loop address setting on the
BACnet

®

Link for the specific loop the VAV/CAV controller resides on

and the second is the VAV/CAV controller address. The BACnet

®

Link

loop address can be either 0, 1, 2 or 3. See Figure 3 at the front of this
manual for detailed information on the BACnet

®

Link loop address

jumper settings.

The second variable value used to calculate the Object Instance number
is the VAV/CAV controller address and is determined by the address
switch settings on the VAV/CAV controller. Valid address settings are 1
through 16.

See Table 10 at the end of this chapter for complete Object Instance
Number calculation information

Object Properties

The information and tables that follow detail the properties and prop-
erty identifiers for the VAV/CAV Object.