Programming - standard objects, Bacnet® link interface technical guide 7, General information – Orion System BACnet Link User Manual
Page 7: Parameters, Instance number base, Mua ii instance number base
BACnet® Link Interface
Technical Guide
7
Programming - Standard Objects
General Information
The BACnet
®
Link provides additional shadowing Analog Input Ob-
jects and Analog Value Objects for read/write parameters of the MUA
II, VAV/CAV and CW/HW controllers.
Note:
The BACnet
®
Link does not implement any operational
function for the Analog Input Object or the Analog Value
Object but only uses the Current Value property of the
Analog Input/Value Object as a vehicle to convey one
specified parameter of the MUA II, VAV/CAV or CW/
HW controller.
Read Only Parameters are represented by Analog Input Objects and
Setpoint Parameters are represented by Analog Value Objects.
Parameters
Parameters for (1) MUA II controller are represented by 36 Analog
Input/Value Objects.
Parameters for (1) VAV/CAV controller are represented by 52 Analog
Input/Value Objects.
Parameters for (1) CW/HW controller are represented by 54 Analog
Input/Value Objects.
Instance Number Base
Each Analog Input/Value Object has an unique Object Instance Num-
ber Base that can be used to identify which parameter the object repre-
sents. The unique Object Instance Numbers are calculated from for-
mula based on the Instance Number Base which are defined in the tables
that follow.
MUA II Instance Number Base
Instance Number Base For MUA II Controller
Parameter
Instance
Number
Base
Represented
By
Object
Limits
Alarm Status
14
Analog Input
Control Status
12
Analog Input
Cooling Deadband
20
Analog Value
2
20
Current Mode
11
Analog Input
Dew Point Reset Limit
27
Analog Value
40
DP Spt.
Dewpoint Setpoint
22
Analog Value
40
80
Enthalpy Deadband
23
Analog Value
3
20
External Heat Position
15
Analog Input
External Heat Proportion
Band
30
Analog Value
1
30
External Relay Group #1
34
Analog Input
External Relay Group #2
35
Analog Input
External Relay Group #3
36
Analog Input
Heating Deadband
21
Analog Value
2
20
Modulate Gas Valve
Position
17
Analog Input
On Board Relay Group
33
Analog Input
Outdoor Air Cooling
Setpoint
3
Analog Input
Outdoor Air Dew Point
5
Analog Input
Outdoor Air Dew Point
Setpoint
6
Analog Input
Outdoor Air Enthalpy
8
Analog Input
Outdoor Air Enthalpy
Deadband
10
Analog Input
Outdoor Air Enthalpy
Setpoint
9
Analog Input
Outdoor Air Heating
Setpoint
4
Analog Input
Outdoor Air Humidity
7
Analog Input
Outdoor Air Temperature
2
Analog Input
Reheat Value Position
18
Analog Input
Schedule Force
32
Analog Value
0
2
Space Humidity
13
Analog Input
Space Humidity At Max
Supply
28
Analog Value
0
100
Space Humidity At Min
Supply
29
Analog Value
0
100
Space Temperature
16
Analog Input
Space Temperature At
Max Supply
25
Analog Value
40
100
Space Temperature At Min
Supply
26
Analog Value
40
100
Supply Air Reset Limit
24
Analog Value
SA
Spt.
SA Spt.
+ 50
Supply Air Setpoint
31
Analog Value
50
90
Supply Air Setpoint Mirror
1
Analog Input
Supply Air Temperature
19
Analog Input
Table 3: Instance Number Base Data For MUA II