beautypg.com

Programming - standard objects, Technical guide bacnet, Link interface 8 mua ii bacnet – Orion System BACnet Link User Manual

Page 8: Property identifier

background image

Technical Guide

BACnet

®

Link Interface

8

MUA II BACnet

®

Property Identifier

The BACnet

®

Link amends the following property identity to BACnet

®

’s

property identifier.

BACnetPropertyIdentifier :

WattBacScheduleState ::= ENUMERATED {

NormalOperation

(0),

ForceOccupied

(1),

ForceUnoccupied

(2)

}

MuaIIControlMode ::= ENUMERATE {

Unoccupied

(0),

RemoteContactOccupied

(1),

NormalScheduleOccupied

(2),

HolidayModeActive

(3),

ScheduleForceOccupied

(4),

ScheduleForceUnoccupied

(5),

CurrentOutputForceMode

(6),

PushButtonOverride

(7)

}

MuaIIControlStatusBits ::= BIT STRING {

CoolingDemand

(0),

HeatingDemand

(1),

DehumidificationDemand

(2),

FanInStartUpDelay

(3),

ProofOfFlow

(4),

SpaceHumiditySensorInstalled

(5),

SpaceTemperatureSensorInstalled

(6),

ExternalHeatConfig

(7),

ReheatRelayConfig

(8),

ModGasIIConnected

(9),

ReheatIIConnected

(10),

}

MuaIIOnBoardRelayBits ::= BIT STRING {

OnBoardRelay1

(0),

OnBoardRelay2

(1),

OnBoardRelay3

(2),

OnBoardRelay4

(3),

OnBoardRelqy5

(4),

}

MuaIIExRelayGroup1Bits ::= BIT STRING {

ExpansionBoard1Relay1

(0),

ExpansionBoard1Relay2

(1),

ExpansionBoard1Relay3

(2),

ExpansionBoard1Relay4

(3),

}

MuaIIExRelayGroup2Bits ::= BIT STRING {

ExpansionBoard2Relay1

(0),

ExpansionBoard2Relay2

(1),

ExpansionBoard2Relay3

(2),

ExpansionBoard2Relay4

(3),

}

MuaIIExRelayGroup3Bits ::= BIT STRING {

ExpansionBoard3Relay1

(0),

ExpansionBoard3Relay2

(1),

ExpansionBoard3Relay3

(2),

ExpansionBoard3Relay4

(3),

}

MuaIIAlarmBits ::= BIT STRING {

BadSupplyAirTemperatureSensor

(0),

NoOutdoorAirTemperatureAvailable

(1),

MissingHumiditySensor

(2),

FanProvingAlarm

(3),

LowSupplyAirTemperature

(4),

HighSupplyAirTemperature

(5),

}

Programming - Standard Objects