Programming - standard objects, Technical guide bacnet, Link interface 8 mua ii bacnet – Orion System BACnet Link User Manual
Page 8: Property identifier
Technical Guide
BACnet
®
Link Interface
8
MUA II BACnet
®
Property Identifier
The BACnet
®
Link amends the following property identity to BACnet
®
’s
property identifier.
BACnetPropertyIdentifier :
WattBacScheduleState ::= ENUMERATED {
NormalOperation
(0),
ForceOccupied
(1),
ForceUnoccupied
(2)
}
MuaIIControlMode ::= ENUMERATE {
Unoccupied
(0),
RemoteContactOccupied
(1),
NormalScheduleOccupied
(2),
HolidayModeActive
(3),
ScheduleForceOccupied
(4),
ScheduleForceUnoccupied
(5),
CurrentOutputForceMode
(6),
PushButtonOverride
(7)
}
MuaIIControlStatusBits ::= BIT STRING {
CoolingDemand
(0),
HeatingDemand
(1),
DehumidificationDemand
(2),
FanInStartUpDelay
(3),
ProofOfFlow
(4),
SpaceHumiditySensorInstalled
(5),
SpaceTemperatureSensorInstalled
(6),
ExternalHeatConfig
(7),
ReheatRelayConfig
(8),
ModGasIIConnected
(9),
ReheatIIConnected
(10),
}
MuaIIOnBoardRelayBits ::= BIT STRING {
OnBoardRelay1
(0),
OnBoardRelay2
(1),
OnBoardRelay3
(2),
OnBoardRelay4
(3),
OnBoardRelqy5
(4),
}
MuaIIExRelayGroup1Bits ::= BIT STRING {
ExpansionBoard1Relay1
(0),
ExpansionBoard1Relay2
(1),
ExpansionBoard1Relay3
(2),
ExpansionBoard1Relay4
(3),
}
MuaIIExRelayGroup2Bits ::= BIT STRING {
ExpansionBoard2Relay1
(0),
ExpansionBoard2Relay2
(1),
ExpansionBoard2Relay3
(2),
ExpansionBoard2Relay4
(3),
}
MuaIIExRelayGroup3Bits ::= BIT STRING {
ExpansionBoard3Relay1
(0),
ExpansionBoard3Relay2
(1),
ExpansionBoard3Relay3
(2),
ExpansionBoard3Relay4
(3),
}
MuaIIAlarmBits ::= BIT STRING {
BadSupplyAirTemperatureSensor
(0),
NoOutdoorAirTemperatureAvailable
(1),
MissingHumiditySensor
(2),
FanProvingAlarm
(3),
LowSupplyAirTemperature
(4),
HighSupplyAirTemperature
(5),
}