Alarm Polling Setup Using Prism 2
Setting Up Alarm Polling for Controllers
In order to set up Alarm Polling to work with the System Manager TS
II, you must have a CommLink and MiniLink Polling Device installed
on your system. The following procedure must be done for the MiniLink
Polling Device on each loop.
In the Loop Selection Window of the Prism 2
Main Screen, select the loop where your Mini-
Link Polling Device is located. Then, in the
Unit Selection Window scroll down to Address
60 - MiniLink PD and click once on your selec-
tion. (Figure 142)
Figure 142: Loop & Unit Selection Windows
Figure 145: Polling Device Setpoints Window
Click the
option at the top far right of the Polling
Device Setpoints Window. The Alarm / Override Polling Window will
appear. (Figure 146)
In the Alarm / Override Polling Window, click the box to the left of
each controller to choose alarm polling and push-button overrides for
that controller. A check mark in the box designates alarm polling/push-
button override.
The Polling Device Window will appear. (Figure 143)
Figure 146: Alarm / Override Polling Window
Click
at the top of the screen. The Polling Device Set-
points Window will appear. (Figure 144)
Figure 143: Polling Device Window
Revised 8/29/11