Page 25: 25 accessing and entering vcm & vcm-x setpoints

SMTS II Technical Guide
VCM & VCM-X Controllers
25
Accessing and Entering VCM & VCM-X
Setpoints
While in the VCM-X Status Screen (see Figure 31), touch the
< Set-
points>
button found on the bottom menu bar. The VCM-X Controller’s
Temperature Setpoints Screen will appear. See Figure 32.
Level 1 and Level 2 users can change occupied space temperature set-
points, but only Level 3 users can change all setpoints.
Accessing and Entering VCM & VCM-X Setpoints
Figure 31: VCM-X Controller Status Screen
Figure 32: VCM-X Controller Temperature Setpoints
Screen
Individual setpoint and confi guration buttons are located at the bot-
tom of the Setpoint Screens. See Figure 33. Simply touch a specifi c
button to access that category.
Within each Setpoint Screen, touch the
< Status>
button to return
to the Status Screen or touch
< Home>
to return to the Main Screen.
Use the
<+>
and
<->
buttons to scroll through the setpoints and
confi gurations. Simply touch the blue highlighted box to change the
setpoint. Each setpoint data entry screen will provide a defi nition of
the setpoint and specifi c instructions for entering the setpoint and
will include the setpoint range as in the example below, Figure 34.
Touch
to have the system accept the new value. If you enter
a setpoint that is not in the valid range, the setpoint will remain as is
and will not change.
Each setpoint data entry screen is self-explanatory; however, each
setpoint and confi guration is explained in the next section, Confi gur-
ing VCM-X Setpoints. To easily reference a particular setpoint or
confi guration, refer to the Index.
Figure 33: VCM / VCM-X Setpoint Buttons
Temps
Static
Staging
Misc
Relays
Config
Figure 34: VCM-X Cooling Mode Setpoint Data Entry
Screen