Vcm, vcm-x & vcb-x controllers, Vcb-x controllers, Vcb-x confi guration – Orion System System Manager TS II In-House User Manual
Page 49: Smts ii technical guide

SMTS II Technical Guide
VCM, VCM-X & VCB-X Controllers
49
VCB-X Controllers
Setpoints for Unit 0001
Configuration
Monitor Return Airflow Sensor
Monitor Supply Airflow Sensor
Monitor Exhaust Airflow Sensor
Monitor Outdoor Airflow Sensor
Control Outdoor Airflow
Has Outdoor Air Temperature Sensor
Page 17 of 19
Ebtron Sensors
Paragon Sensors
Figure 91: VCB-X Relay Confi guration Screen 18
Installed Sensors
Touch the square button to select the desired airfl ow sensor monitoring:
Monitor Return Airfl ow Sensor—
Select
this item if
you have an Airfl ow Monitoring station
measuring the CFM
of the Return Air airfl ow stream of this unit
. Default is NO.
Monitor Supply Airfl ow Sensor—
Select
this item if
you have an Airfl ow Monitoring station
measuring the CFM
of the Supply Air airfl ow stream of this unit
. Default is NO.
Monitor Exhaust Airfl ow Sensor—
Select
this item if
you have an Airfl ow Monitoring station
measuring the CFM
of the Exhaust Air airfl ow stream of this unit
. Default is NO.
Monitor Outdoor Airfl ow Sensor—
Select
this item if
you have an Airfl ow Monitoring station
measuring the CFM
of the Outdoor Air airfl ow stream of this unit
. Default is NO.
Control Outdoor Airfl ow—
Select
this item if
you have an Airfl ow Monitoring station and are controlling the
OA Damper to an airfl ow (CFM) setpoint. Default is NO.
Has Outdoor Air Temperature Sensor—
Select
this
item if you have any type of Outdoor Air Temperature Sensor
installed.
Type of Monitoring Station
Touch the radio button to select the type of airfl ow monitoring station:
EBTRON Sensors
—Select this item if using an Ebtron or
Greentrol Airfl ow Monitoring Station.
Paragon Sensors
—Select this item if using a Paragon
Airfl ow Monitoring Station.
VCB-X Confi guration
Setpoints for Unit 0001
Configuration
Broadcast Outdoor Air Humidity
Broadcast Outdoor Air Temperature
Broadcast Commands to VAV Boxes
Broadcast Building Pressure
Page 18 of 19
Figure 92: VCB-X Relay Confi guration Screen 19
Setpoints for Unit 0001
Configuration
Page 19 of 19
Glycol Percentage for Water Source Heat Pumps
0% 32.0 Deg Freezing Point
5% 29.1 Deg Freezing Point
10% 26.1 Deg Freezing Point
15% 22.9 Deg Freezing Point
20% 19.2 Deg Freezing Point
25% 14.7 Deg Freezing Point
30% 9.2 Deg Freezing Point
35% 2.4 Deg Freezing Point
40% -6.0 Deg Freezing Point
Figure 93: VCB-X Relay Confi guration Screen 20
Broadcast Outdoor Air Humidity—
The VCB-X will
broadcast its Outdoor Air Humidity Reading to other HVAC
units if they are not equipped with their own Outdoor Air RH
sensors. A network communications device (MiniLink PD or
CommLink) is needed in order for this feature to operate.
Broadcast Outdoor Air Temperature—
The VCB-X will
broadcast its Outdoor Air Temperature Reading to other HVAC
units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device
(MiniLink PD or CommLink) is needed in order for this feature
to
operate.
Broadcast Commands to VAV Boxes—
The VCB-X will
broadcast all applicable information and commands to the VAV
Boxes.
Broadcast Building Pressure—
The VCB-X will broadcast
Building Pressure from this unit to any other unit requiring this
value.
Glycol Percentage for Water Source Heat Pumps
Select the percentage that applies to your unit.