Vcm & vcm-x controllers, Vcm-x miscellaneous setpoints, Smts ii technical guide 40 – Orion System System Manager TS II In-House User Manual
Page 40

VCM & VCM-X Controllers
SMTS II Technical Guide
40
VCM-X Miscellaneous Setpoints
Setpoints for Unit 0102
Space Sensor Offset
Outdoor Sensor Offset
0.0
0.0
Supply Sensor Offset
Return Sensor Offset
0.0
0.0
Miscellaneous
°F
°F
°F
°F
Page 5 of 5
Coil Temperature Offset
0.0
°F
Figure 67: VCM-X Miscellaneous Setpoints Screen 5
Space Sensor Offset
If the Space Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Space Temperature
Sensor reading and a negative value to lower the Sensor reading. High limit
= 100ºF; Low limit = -100ºF; Default = 0ºF.
Supply Sensor Offset
If the Supply Air Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Supply Air Tempera-
ture Sensor reading and a negative value to lower the Sensor reading. High
limit = 100ºF; Low limit = -100ºF; Default = 0ºF.
Return Sensor Offset
If the Return Air Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Return Air Temperature
Sensor reading and a negative value to lower the Sensor reading. High limit
= 100ºF; Low limit = -100ºF; Default = 0ºF.
Outdoor Sensor Offset
If the Outdoor Air Temperature Sensor is reading incorrectly, you can use
this option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Outdoor Air Tem-
perature Sensor reading and a negative value to lower the Sensor reading..
High limit = 100ºF; Low limit = -100ºF; Default = 0ºF.
Coil Temperature Offset
If the Coil Temperature reading needs to be adjusted, enter a positive value
to raise the Coil Temperature reading and a negative value to lower the Coil
Temperature reading. High limit = 30ºF; Low limit = -30ºF; Default = 0ºF.