beautypg.com

Orion System MUA II D Controllers Operator Interfaces User Manual

Page 9

background image

Operator Interfaces

Technical Guide

9

EXAMPLE #2
You would like to view the 12th controller on the 24th loop. Enter “2412”
as the Unit ID

EXAMPLE #3
You would like to view the only controller on the loop. Enter 1 as the
Unit ID. No loop number is required since there is only one loop.

Hit the “Enter” key after entering the unit ID. If you are using the Modular
Service Tool you will be taken directly to the first screen for the opera-
tion you are trying to program.

System Manager Passcodes

Anytime you enter a unit ID with the Modular System Manager you
will be asked for a passcode. Passcodes are not required to view Status
Screens. The screen below will appear if this action requires passcode
clearance.

THIS ACTION REQUIRES
PASSCODE CLEARANCE

Enter Passcode: xxxx

The System Manager has two levels of user access. Level 1 users are
limited to viewing or changing the Time and Date and Operating Sched-
ules. Level 2 users have complete system access. Any status or setpoint
field can be read or reset from the System Manager.

These two levels of passcodes are programmable by any Level 2 user.
The default Level 1 passcode is “1111” and the default Level 2 passcode
is “2222.”

If you wish to change either Level 1 or Level 2 passcodes please see the
instructions that follow.

From the main status screen press "Enter", The following screen will
appear.

1) Set Time & Date
2) Communications

->) Next Menu
ESC) Exit Menu

Press ">", to proceed to the next menu and the following screen will
appear.

1) Change Passcodes
2) Loop Search

<-) Prev. Menu
ESC) Exit Menu

Press the “1” key on the keypad to enter the Change Passcode screen.

THIS ACTION REQUIRES
PASSCODE CLEARANCE

Enter Passcode: xxxx

Enter the default Level 2 passcode “2222” to access the next screen.
You must use the Level 2 passcode to change passcodes. Level 1
passcodes will not allow changing passcodes!

Enter New Passcode
Level 1.....: xxxx
Level 2.....: xxxx
[Must Be 4 Digits]

This screen allows you to enter new Level 1 or Level 2 passcodes. The
actual digits in your passcodes are never displayed. An “X” is used as a
place holder for each digit entered. Passcodes must always be four dig-
its in length, so the usable range of numbers is 1000 to 9999.

Caution:

If you change the Level 2 passcode and cannot
remember what it is, you will be locked out of
your system!