beautypg.com

General programming information – Orion System MUA II D Controllers Operator Interfaces User Manual

Page 12

background image

Technical Guide

Operator Interfaces

12

General Programming Information

controller on the system and press "Enter". The following screen will
appear.

Overrides Screen

SEARCHING!

After the System Manager or Modular Service Tool completes its search,
it will list the first unit on the system that is currently in the override
mode. Press the previous or next button to scroll through all units that
are in the Override Mode.

Overrides Screen
Loop = 1 Unit = 59

Override Unit

Alarm Search

The System Manager or the Modular Service Tool can be used to search
for all active alarms on the system. From either of the operators inter-
faces press the “Alarm” key. The Unit Selection screen below will be
displayed. Enter the Unit ID of any unit on the system and press “En-
ter”.

Unit Selection
Enter Unit ID#

Selected ID#: xxxx

The following screen will appear. The operators interface will search
for any active alarms on the entire system.

Alarm Screen

SEARCHING!

After the System Manager or Modular Service Tool completes it’s search,
it will list the first unit on the system that currently has an active alarm.
Press “Enter” to scroll through all the alarms on that particular unit. To
move to the next unit or back to the previous unit use the “Prev” or
“Next” arrows to move between units with alarms.

Alarm Search Screen
Loop = 1 Unit = 59

Space Sensor Failure

To clear any alarms that are found you must fix the problem indicated in
the alarm. Once the problem is fixed, the alarm will clear from the screen
the next time the unit is polled.