from the Supply Air Setpoint gives the Unoccupied Heating Mode
Setpoint.
When the Space Air Temperature drops below this setpoint,
the MUA II D will go to Unoccupied Heating Mode.

If the default setpoint of 30° F is used it will cancel the corresponding
unoccupied cooling or unoccupied heating mode.

Description

Minimum

Default

Maximum

Unoccupied Cooling

Deadband

Cooling

Deadband

Setpoint

30° F

30° F

Unoccupied Heating

Deadband

Heatling

Deadband

Setpoint

30° F

30° F

Setpoint Screen #4

MUA II Spts IDxxxx
Systems With Re-heat

Dewpoint Control
Setpoint...: xxx°F

The systems capable of dehumidification will enter this mode of opera-
tion when the Outside Air Dewpoint rises above the Dewpoint Setpoint.

Description

Minimum

Default

Maximum

Dewpoint Setpoint

40° F

55° F

80° F

Setpoint Screen #5

MUA II Spts IDxxxx
Enthalpy Staging

Deadband....: xxxBTU
Hysterisis..: x.xBTU

The Enthalpy Deadband if the amount Enthalpy in the Outside Air
needed to activate an extra stage of cooling. The Enthalpy Hysterisis
is use to avoid unnecessary cycling of the cooling stages when the Out-
side Enthalpy
is close to the setpoint.

Description

Minimum

Default

Maximum

Enthalpy Deadband

3 BTU

5 BTU

20 BTU

Enthalpy Hysterisis

0.5 BTU

1 BTU

2.5 BTU

Setpoint Screen #6

MUA II Spts IDxxxx
Heat Delay During

Dehumidifcation
Will Occur..: xxxMin

If heating during dehumidification is configured, this is the amount of
time the heating call will be delayed after the dehumidification is acti-
vated.

Description

Minimum

Default

Maximum

Heat Delay

0 Min

2 Min

10 Min

Setpoint Screen #7

MUA II Spts IDxxxx
Alarm Limits

Hi SAT Limit.: xxx°F
Lo SAT Limit.: xxx°F

If the Supply Air Temperature ever rises above the Hi SAT Limit or
drops below the Lo SAT Limit for a user defined period of time, an
alarm is generated.

Description

Minimum

Default

Maximum

Hi SAT Limit

50° F

150° F

150° F

Lo SAT Limit

0° F

0° F

70° F

Setpoint Screen #8

MUA II Spts IDxxxx
Supply Air Alarms If

Out Of Range For
xxx Minutes

This is the amount of time the Supply Air Temperature must be outside
either the Hi or Lo SAT Limit setpoint before it generates an alarm.

Description

Minimum

Default

Maximum

Minutes

0 Min

30 Min

300 Min