Programming the mua ii d controller, Technical guide operator interfaces 16 – Orion System MUA II D Controllers Operator Interfaces User Manual

Page 16

background image

Technical Guide

Operator Interfaces

16

Setpoint Screen #9

MUA II Spts IDxxxx
Set Sat Temp Reset

SPC= xxx Spt= xxx
SPC= xxx Rst= xxx

A Type III Thermistor Sensor connected to AIN 1 can be used to reset
the Supply Air Temperature. This screen allows the user to set the tem-
perature that the reset will begin at and the new reset Supply Air Tem-
perature range.

Description

Minimum

Default

Maximum

Minimum Range

40° F

0° F

100° F

Maximum Range

40° F

0° F

100° F

Reset

SAT Spt

SAT Spt

Spt + 50° F

Setpoint Screen #10

MUA II Spts IDxxxx
Set Dewpoint Reset

HUM= xxx Spt= xxx
HUM= xxx Rst= xxx

An Indoor Humidity Sensor connected to AIN7 can be used to reset the
Dewpoint Setpoint. This screen allows the user to set the relative hu-
midity percentage that the reset will begin at, and the new reset Dewpoint
Setpoint percentage range.

Description

Minimum

Default

Maximum

Minimum Range

0%

0%

100%

Maximum Range

0%

0%

100%

Reset

35° F

55° F

Dewpoint Spt

Setpoint Screen #11-14

MUA II Spts IDxxxx
Cooling Stage Delays

Staging Up : xx Min
Staging Down: xx Min

MUA II Spts IDxxxx
Cooling Stage Delays

Min Run Time: xx Min
Min Off Time: xx Min

MUA II Spts IDxxxx
Heating Stage Delays

Staging Up : xx Min
Staging Down: xx Min

MUA II Spts IDxxxx
Heating Stage Delays
Min Run Time: xx Min

Min Off Time: xx Min

Both the Heating Stages and the DX Cooling Stages utilize Staging Up
and Down delay periods between stages and Minimum Run Times and
Off Times.

Both modes have their own set of staging and run delay times. The
Heating timer screens look exactly the same as the cooling except they
reference the Heating instead of Cooling.

See the Sequence of Operation Manual for information on how these
delays and run times are used.

Description

Minimum

Default

Maximum

Cooling Stage Up

3 Min

3 Min

15 Min

Cooling Stage Down

1 Min

1 Min

15 Min

Cooling Min Run Time

5 Min

5 Min

15 Min

Cooling Min Off Time

3 Min

3 Min

15 Min

Heating Stage Up

3 Min

3 Min

15 Min

Heating Stage Down

1 Min

1 Min

15 Min

Heating Min Run Time

2 Min

2 Min

15 Min

Heating Min Off Time

1 Min

1 Min

15 Min

Setpoint Screen #15

MUA II Spts IDxxxx
External Mod Heat

DeadBand.....: xxx°F

The External Heat Proportional deadband is the range through which
the external heating device will proportionally modulate.

Description

Minimum

Default

Maximum

Proportional Band

1° F

5° F

30° F

Programming The MUA II D Controller