Appendix, Technical guide hb mini controller 20 – Orion System HB Mini User Manual
Page 20

Technical Guide
HB Mini Controller
20
Appendix
The HB Mini Controller has many setpoints that are user adjustable.
This adjustability allows the installer complete control of all major unit
operating characteristics during the setup and commissioning phase of
the HB unit installation. It also allows a service technician the ability to
change setpoints to monitor and record unit operation to determine if
the unit is functioning as specified. The tables that follow show the
available setpoints for each classification or control group provided on
the HB Mini Controller.
Cooling Control Setpoints
Description
Min.
Default
Max.
Cooling Stages
1
2
2
Minimum Off Time
180 Sec
180 Sec
900 Sec
Minimum On Time
300 Sec
300 Sec
900 Sec
Staging Up Delay Interval
180 Sec
180 Sec
900 Sec
Staging Down Delay Interval
60 Sec
60 Sec
900 Sec
Low Pressure Delay Period
5 Sec
30 Sec
60 Sec
Low Pressure Safety
5 Sec
5 Sec
30 Sec
Low Pressure Max. Trip Point
1
3
5
Fan Off Delay Period
1 Sec
45 Sec
120 Sec
Auto Staging Up Delay
180 Sec
600 Sec
900 Sec
Table 4: Cooling Control Setpoints
Heating Control Setpoints
Description
Min.
Default
Max.
Heating Stages
1
3
3
Minimum Off Time
60 Sec
60 Sec
900 Sec
Minimum On Time
120 Sec
120 Sec
900 Sec
Staging Up Delay Interval
180 Sec
180 Sec
900 Sec
Staging Down Delay Interval
60 Sec
60 Sec
900 Sec
Heat Safety Maximum Count
1
3
5
Fan Off Delay Period
1 Sec
120 Sec
180 Sec
Auto Stage Up Delay
180 Sec
600 Sec
900 Sec
Table 5: Heating Control Setpoints
Temperature Control Setpoints
Description
Min.
Default
Max.
Cooling Lockout
Temperature
32° F
40° F
80° F
Heating Lockout
Temperature
40° F
80° F
120° F
Table 6: Temperature Control Setpoints
Miscellaneous Control Setpoints
Description
Min.
Default
Max.
Force Mode Timer
1 Min
60 Min
240 Min
Table 7: Miscellaneous Control Setpoints