Programming with the hb service tool, Technical guide hb mini controller 16 – Orion System HB Mini User Manual
Page 16

Technical Guide
HB Mini Controller
16
Heating Module Setpoint Screens
The Heating Module Setpoints Screens are accessed by navigating to
the Heating Module and then pressing the ENTER key. The following
screen will then appear.
Status
Setpoints
Press the down SELECT arrow key until “Setpoints” is on the top line
of the screen and then press the ENTER key. Press the down SELECT
arrow key or up SELECT arrow key to move forward or backward
through the Heating Module Setpoint screens.
Please see the Appendix section in the back of this manual for Tables
listing the minimum, maximum and default setpoints for all of the
setpoint screens.
Heating Stages Quantity
Heat Stages
X
Adjust the quantity of Heating Stages and then press the ENTER key.
Outdoor Air Temperature Heating Lockout
OAT Heat Lockout
XXX F
Adjust the Outdoor Air Temperature Heating Lockout and then press
the ENTER key.
Heating Minimum Off Time
Heat Min Off
XXX Sec
Adjust the desired Heating Minimum Off Time and then press the
ENTER key.
Heating Minimum On Time
Heat Min On
XXX Sec
Adjust the desired Heating Minimum On Time and then press the EN-
TER key.
Heating Stage Up Delay
Heat Stage Up
XXX Sec
Adjust the desired Heating Stage Up Delay time and then press the
ENTER key.
Heating Stage Down Delay
Heat Stage Down
XXX Sec
Adjust the desired Heating Stage Down Delay time and then press the
ENTER key.
Heat Safety Monitor Maximum Trips
HSM Max Trips
X
The Heating Safety Maximum Trips is a factory setting and should not
be changed unless authorized to do so by WattMaster or AAON
®
Tech-
nical Support.
Heating Fan Off Delay
Heat Fan Off Dly
XXX Sec
The Heating Fan Off Delay is a factory setting and should not be changed
unless authorized to do so by WattMaster or AAON
®
Technical Sup-
port.
Auto Stage Up Time
Auto Stage Up
XXX Sec
The Auto Stage Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.
Alarm Module Status Screens
The Alarm Module Status Screens are accessed by navigating to the
Alarm Module and pressing the ENTER key. Setpoints are not avail-
able for the Alarm Module. After pressing ENTER the following screen
will appear.
Programming With The HB Service Tool