Hb mini controller technical guide 15 – Orion System HB Mini User Manual
Page 15

HB Mini Controller
Technical Guide
15
Cooling Fan Off Delay
Cool Fan Off Dly
XXX Sec
The Cooling Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON
®
Techni-
cal Support.
Auto Stage Up Time
Auto Stage Up
XXX Sec
The Auto Stage Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.
Heating Module Status Screens
The Heating Module Status Screens are accessed by navigating to the
Heating Module screen and pressing the ENTER key. The following
screen will then appear.
Status
Setpoints
Select “Status” by pressing the ENTER key. Press the up or down SE-
LECT arrow key to move forward or backward through the Heating
Module Status screens.
Heating Stage 1 Energized
W1-Active
NO
Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W1”.
Heating Stage 2 Energized
W2-Active
NO
Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W2”.
Heating Stage 3 Energized
W3-Active
NO
Line #2 displays “YES” if there is a 24 VAC signal on HB Mini Con-
troller terminal “W3”.
Fan Status
Fan Status
Fan Off
Line #2 displays the current Supply Fan Status. If the Supply Fan is
on, line #2 displays either “Fan Low Speed” or “Fan High Speed”.
Heating Relay #1
Heat 1 Relay
OFF
Line #2 displays “ON” if Heating Relay #1 is active.
Heating Relay #2
Heat 2 Relay
OFF
Line #2 displays “ON” if Heating Relay #2 is active.
Heating Relay #3
Heat 3 Relay
OFF
Line #2 displays “ON” if Heating Relay #3 is active.
Heat Safety Monitor
HSM
CLOSED
Line #2 displays “OPEN” anytime the Heat Safety Monitor is open.