Page 8: Description, Mounting

Form: Orion-OE520XX-M-RndDmpr-Sub-01G
Page
1 of 2
Description
The OE520-XX-M Round Pressure
Dependent Zone Damper Assembly with
modular connectors consists of a round
air damper and Zone Controller Actuator
Package with modular wiring connectors.
An optional Zone Controller Expansion
Module (OE325-01) is available for
control of reheat, heat and/or control of
series or parallel flow fan terminal units.
The Zone Controller board is
microprocessor based and communicates
with the HVAC unit controller on the Orion
network communications loop. The Zone
Controller monitors the space
temperature and allocates the proper
airflow into its assigned space to achieve
the desired comfort and ventilation levels.
Pressure Dependent Zone Dampers are
used in air conditioning systems that do
not require pressure independent airflow
control. If your system requires pressure
independent control of the airflow, see the
“OE521-XX-M Round Pressure
Independent Zone Damper” submittal sheet for the correct specifications. All dampers are tested for performance
in accordance with AMCA 500D standards.
Mounting
The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow
direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation
should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper
should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control
enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or
bottom of the ductwork. Adequate clearance should be maintained between the control panel and any
obstruction to allow for removal of the control panel cover and access to the controls.
OE520-XX-M Round P.D.
Zone Damper
Assembly W/ Modular Connectors
Technical Data
OE520-XX-M Round Pressure Dependent
Zone Damper Assembly W/ Modular Connectors
Zone Controller:
Air Damper Construction:
Supply Power
24 Volt AC
Damper Body
20 Ga. Galv. Steel
Power Consumption
6 VA Maximum
Damper Blade
Round -18 Ga. Galv. Steel
Operating Temperature
35
F to 125F
Damper Bearings
Stainless Steel
Operating Humidity
90% RH Non-Condensing
Damper Seal
EPDM Rubber Gasket
Communications
RS-485 - 9600 Baud
Leakage
< 20 CFM Per Sq. Ft. @ 4” SP
Insulation
½” Foil Faced Fiberglass
Inputs:
Dimensions:
Room Temperature Sensor
Air Damper Model
“A”
“B”
“C”
Setpoint Adjustment
OE510-06 (6”)
23.00
5.88
9.88
Actuator Position Feedback
OE510-08 (8”)
23.00
7.88
12.13
Communication Connectors:
Modular In & Out
OE510-10 (10”)
23.00
9.88
14.31
Outputs:
OE510-12 (12”)
23.00
11.88
16.43
Expansion Port for Auxiliary Relay Board
OE510-14 (14”)
23.00
13.88
18.50
Actuator Port for Connection to Damper Actuator
OE510-16 (16”)
23.00
15.88
20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components
One Year Warranty On Air Damper