Orion-oe523-rdslavedmpr-sub-01e, Oe523-xx round slaved zone damper assembly, Description – Orion System OE742-XX-VAVZ User Manual
Page 18: Mounting

Form: Orion-OE523-RdSlaveDmpr-Sub-01F
Page
1 of 2
Description
The OE523-XX Round Slaved Zone
Damper Assembly, consists of a round air
damper, actuator, (1) slave wiring interface
card mounted in the enclosure and also
includes (1) slave wiring interface card kit
shipped loose for field mounting to the
master zone damper assembly. This kit
contains a slave wiring interface card and a
cable.
The Round Slaved Zone Damper
Assembly is used in systems when it is not
possible or practical to use a single large
Zone Damper to satisfy the zone's CFM
requirements.
A total of two Slaved Zone Dampers may
be used in conjunction with a master Zone
Damper. The Slave Damper(s) are wired in
parallel with the master Zone Damper and
track the movement of the master Zone
Damper. Connection of the master Zone
Damper requires a slave wiring interface
kit, which is shipped loose for field
mounting to the master Zone Damper and
is supplied with each Slaved Zone
Damper. The kit connects the Zone
controller on the master to the master
actuator and provides wiring terminals for
wiring to the Slaved Zone Dampers. Only (1) of these kits is required for each master/slave installation. All
dampers are tested for performance in accordance with AMCA 500D standards.
Mounting
The Slaved Zone Damper Assembly should be mounted according to standard duct installation practices with air
flow direction as shown in the illustration above. After installation of the Air Damper in the ductwork, insulation
should be applied around any remaining un-insulated surface on the air valve inlet and outlet. The Air Damper
should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control
enclosure in a vertical plane. Do not mount the Air Damper Assembly with the control enclosure on the top or
bottom of the ductwork. Adequate clearance should be maintained between the control panel and any
obstruction to allow for removal of the control panel cover and access to the controls.
OE523-XX Round Slaved Zone
Damper Assembly
Technical Data
OE523-XX Round Slaved
Zone Damper Assembly
Actuator:
Air Damper Construction:
Supply Power
24 Volt AC
Damper Body
20 Ga. Galv. Steel
Power Consumption
3.4 VA Maximum
Damper Blade
Round -18 Ga. Galv. Steel
Operating Temperature
35
°F to 125°F
Damper Bearings
Stainless Steel
Operating Humidity
90% RH Non-Condensing
Damper Seal
EPDM Rubber Gasket
Position Feedback (Bypass)
10Kohm, 1 W Potentiometer
Leakage
< 20 CFM Per Sq. Ft. @ 4” SP
Insulation
½” Foil Faced Fiberglass
Dimensions:
Air Damper Model
“A”
“B”
“C”
Air Damper Model
“A”
“B”
“C”
OE513-06 (6”)
23.00
5.88
9.88
OE513-12 (12”)
23.00
11.88
16.43
OE513-08 (8”)
23.00
7.88
12.13
OE513-14 (14”)
23.00
13.88
18.50
OE513-10 (10”)
23.00
9.88
14.31
OE513-16 (16”)
23.00
15.88
20.56
WattMaster reserves the right to change specifications without notice
Three Year Warranty On Electronic Components
One Year Warranty On Air Damper