Orion-oe742-32-vavz-zcap-sub-01a, Description, Mounting – Orion System OE742-XX-VAVZ User Manual
Page 2

Form:
Orion-OE742-32-VAVZ-ZCAP-Sub-01B.doc
Page
1 of 1
Description
The OE742-32-VAVZ
VAV/Zone Controller Actuator
Package with Terminal Block
connectors provides a new so-
lution for zone damper applica-
tions. The new package in-
cludes a VAV/Zone Actuator
and a VAV/Zone Controller
mounted in a plastic enclosure.
An optional conduit cover is
also available that mounts over
the control terminals for installa-
tions requiring conduit connec-
tions. The VAV/Zone Controller
Actuator Package is designed
for left- or right-hand mounting
on a VAV Terminal unit. Each
package comes standard with a
right-hand label and the actua-
tor positioned for right-hand
use. For left-hand units, the
actuator can be rotated 180
degrees by removing two
screws that secure it to the en-
closure, rotating the damper
actuator, and re-fastening the
actuator to the enclosure. A left-
hand label is also supplied that
can be applied over the right-
hand label for left-hand applica-
tions.
Mounting
The VAV/Zone Actuator pack-
age is very easy to mount on
your terminal unit. It is installed
by simply loosening the damper shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly
over the terminal unit’s damper shaft, tightening the actuator u-bolt around the damper shaft, and inserting a self-tapping
screw into the anti-rotation bushing located at the opposite end of the enclosure base. Detailed mounting and installation in-
structions are provided with each package. A conduit enclosure is available as an option which provides conduit knockouts
and encloses the electrical connections for applications where code requirements mandate conduit be used for low voltage
electrical wiring.
OE742-32-VAVZ VAV/Zone
Controller Actuator Package
Technical Data
OE742-32-VAVZ VAV/Zone Controller Actuator Package
Zone Controller:
Outputs:
Supply Power
24 VAC
(1) RJ-45 Cable Connection For Auxiliary Relay Board
Power Consumption
6 VA Maximum
(1) RJ-45 Cable Connection To Damper Actuator
Operating Temperature
10
F to 149F
Uses Same 3 Conductor Terminal Block as Comm Input
Operating Humidity
90% RH Non-
Condensing
Features:
Communications
RS-485 – 9600 Baud
Programming Port
Mini-DIN Jr. Port
Enclosure Material
Fire Rated ABS Plastic
Inputs:
Zone Controller
Factory Mounted Inside The Enclosure
(1) RJ-45 Cable Connection For Digital Temperature
Or Analog Temperature
Zone Actuator
Factory Mounted To The Enclosure
Actuator Rating
35 in/lbs (6 ft
2
Damper Area Max.)
(2) Auxiliary Terminals For Duct Temperature
Sensor
Labeling
Right Hand & Left Hand
(1) Terminal Block Connector For Power In
Airflow Ports
Barbed Tube Fittings (PI Versions Only)
(1) Terminal Block Connector For Comm In
WattMaster reserves the right to change specifications without notice.
Three Year Warranty