Technical Guide

MUA II Controller

20

Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors

Temp

(

º

F)

Resistance

(Ohms)

Voltage @

Input (VDC)

Temp

(

º

F)

Resistance

(Ohms)

Voltage @

Input (VDC)

Temp

(

º

F)

Resistance

(Ohms)

Voltage @

Input (VDC)

-10

93333

4.620

60

14681

3.042

86

8153

2.297

-5

80531

4.550

62

14014

2.985

88

7805

2.242

0

69822

4.474

64

13382

2.927

90

7472

2.187

5

60552

4.390

66

12758

2.867

95

6716

2.055

10

52500

4.297

68

12191

2.810

100

6047

1.927

15

45902

4.200

69

11906

2.780

105

5453

1.805

20

40147

4.095

70

11652

2.752

110

4923

1.687

25

35165

3.982

71

11379

2.722

115

4449

1.575

30

30805

3.862

72

11136

2.695

120

4030

1.469

35

27140

3.737

73

10878

2.665

125

3656

1.369

40

23874

3.605

74

10625

2.635

130

3317

1.274

45

21094

3.470

75

10398

2.607

135

3015

1.185

50

18655

3.330

76

10158

2.577

140

2743

1.101

52

17799

3.275

78

9711

2.520

145

2502

1.024

54

16956

3.217

80

9302

2.465

150

2288

0.952

56

16164

3.160

82

8893

2.407

58

15385

3.100

84

8514

2.352

Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while discon-
nected from the controllers (not powered).

Use the voltage column to check sensors while connected to powered
controllers. Read voltage with meter set on DC volts. Place the “-”(mi-

nus) lead on GND terminal and the “+”(plus) lead on the sensor input
terminal being investigated.

If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.

Appendix

Sensor Checks
The following sensor voltage and resistance tables are provided to aid
in checking sensors that appear to be operating incorrectly. Many sys-
tem operating problems can be traced to incorrect sensor wiring. Be
sure all sensors are wired per the wiring diagrams in this manual.

If the sensors still do not appear to be operating or reading correctly,
check voltage and/or resistance to confirm that the sensor is operating
correctly per the tables. Please follow the notes and instructions below
each chart when checking sensors.