System-40-bac enclosure label, System-40-bac wiring diagram – ONICON System-40-BAC BTU User Manual

Page 27

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

System-40-BAC BTU Meter Manual 03/15 - 1045-2

Page A-1

SYSTEM-40-BAC WIRING DIAGRAM

1 2 3 4 5 6 7 8 1 2 3

10

9

H5

SERIAL

TB3

TB2

H3

4321

4321

1 2 1 2 1 2 1 2

TB8

TB7

TB6

TB5

SW6 SW7 SW2 SW1

C34

C33

R6

DS3

R8 H2 SERIAL

2

1

GRD

DS2

R60

3

JMP5

1

CAUTION

INST

ALL

+ SIDE UP

CR2032 BA

TTER

Y

BA

T1

Internal RTD

(Flow)

External RTD

24V AC/DC

(+)

24V COMMON (-)

AUX 1 (+)

AUX 1 (-)

AUX 2 (+)

AUX 2 (-)

AUX 3 (+)

AUX 3 (-)

RS485 (+)

RS485 (-)

RS485 COMMON

TB1

TB4

COMMISSIONING

MICROPROCESSOR

RESET

RS485 Termination

1 - 2 = 120 Ω

2 - 3 = None

System-40-BAC Enclosure Label

1048 / 33354

02-15

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699

www.onicon.com • [email protected]

Actual Size - 4.125” x 2.875”

Cutline

Flow (external) Temperature Sensor*

Name

Terminal #

Description

1000 ohm

TB2-1

RTD signal wire

Not used

TB2-2

No Connection

Not used

TB2-3

No Connection

1000 ohm RTD

TB2-4

RTD signal wire

Remote (internal) Temperature Sensor

Name

Terminal #

Description

1000 ohm

TB3-1

RTD signal wire

Not used

TB3-2

No Connection

Not used

TB3-3

No Connection

1000 ohm RTD

TB3-4

RTD signal wire

Power and Signal Inputs (18 - 22 AWG wire)

Name

Terminal #

Description

24V ac/dc (+)

TB1-1

12 - 36Vac, 50/60Hz, 15 VA max.

12-42Vdc, 15W max.

24V ac/dc Common (-)

TB1-2

Aux Pulse Input # 1 (+)

TB1-3

For use with open collector

sinking and dry contact ouputs

Pulse Duration: 50ms min.

Sinking Current: 1mA max.

Aux Pulse Input # 1 (-)

TB1-4

Aux Pulse Input # 2 (+)

TB1-5

Aux Pulse Input # 2 (-)

TB1-6

Aux Pulse Input # 3 (+)

TB1-7

Aux Pulse Input # 3 (-)

TB1-8

RS485 (20 - 24 AWG wire)

Name

TB4

Description

RS485 B (+)

TB4-1

RS485 Unit Load = 1/4

Recommended Devices

per Segment = 32

RS485 A (-)

TB4-2

RS485 Common

TB4-3

RS485 Termination Resistor

Name

JMP5

Description

120 ohm

Position 1 Jumper Position 1 & 2

= 120 ohms

120 ohm

Position 2

None

Position 3 Jumper Position 2 & 3

= No Termination

* This sensor must be in the same pipe as the flow sensor.