System-40-BAC BTU Meter Manual 03/15 - 1045-2

Page

10

IMPORTANT NOTE

The flow sensor body must be correctly oriented with respect to the direction of flow in the pipe.

Meters installed with flow in the reverse direction will not function.

i

The calculator enclosure may be rotated around the axis of the flow sensor into three different
positions. To rotate, temporarily slide the enclosure off the flow sensor mounting brackets.
Remove the two retaining screws and reposition the mounting brackets as required. Reinstall
the enclosure with the display properly oriented for viewing. Mounting tracks on the back of
the enclosure allow for mounting in any orientation.

Flow Direction

The sensor port is always on

the downstream end of meter.

Retaining Nut

Seal

Coupling

Slide calculator

enclosure to

remove from

sensor mounting

brackets

Slide Enclosure

Mounting Tracks

Retaining

Screw

Retaining

Screw

IMPORTANT NOTE

When installing the meter in a vertical pipe with upward flow you must rotate the enclosure back

plate 180° when rotating the display 90°. To accomplish this, temporarily remove the 4 cover

screws and rotate the backing plate.

i

The flow sensor is installed with threaded meter couplings and flat sealing gaskets as shown
below. Orient the sensor body by aligning the flow direction arrow with the direction of flow
in the pipe.